Step 8 - Install Outside Air Hood - Bryant Legacy 558J 08-16 Installation Instructions Manual

Table of Contents

Advertisement

Fig. 12 — Horizontal Conversion Panels
Step 8 — Install Outside Air Hood
558J*08-14 UNIT SIZES
Economizer and Two Position Damper Hood Package
Removal and Setup
Factory Option)
(
1. The hood is shipped in knock-down form and must be
field assembled. The indoor coil access panel is used as
the hood top while the hood sides, divider and filter are
packaged together, attached to a metal support tray using
plastic stretch wrap, and shipped in the return air com-
partment behind the indoor coil access panel. The hood
assembly's metal tray is attached to the basepan and also
attached to the damper using two plastic tie-wraps.
2. To gain access to the hood, remove the filter access panel.
(See Fig. 13.)
FILTER ACCESS PANEL
Fig. 13 — Typical Access Panel Locations
3. Locate the (2) screws holding the metal tray to the base-
pan and remove. Locate and cut the (2) plastic tie-wraps
securing the assembly to the damper. (See Fig. 14.) Be
careful to not damage any wiring or cut tie-wraps secur-
ing any wiring.
INDOOR COIL ACCESS PANEL
4. Carefully lift the hood assembly (with metal tray) through
the filter access opening and assemble per the steps out-
lined in Economizer Hood and Two-Position Damper
Hood.
Fig. 14 — Economizer and Two-Position Damper Hood
Economizer Hood and Two-Position Damper Hood
NOTE: If the power exhaust accessory is to be installed on the
unit, the hood shipped with the unit will not be used and must
be discarded. Save the aluminum filter for use in the power
exhaust hood assembly.
1. The indoor coil access panel will be used as the top of the
hood. Remove the screws along the sides and bottom of
the indoor coil access panel. See Fig. 15.
INDOOR
COIL
ACCESS
PANEL
Fig. 15 — Indoor Coil Access Panel Relocation
2. Swing out indoor coil access panel and insert the hood
sides under the panel (hood top). Use the screws provided
to attach the hood sides to the hood top. Use screws pro-
vided to attach the hood sides to the unit. See Fig. 16.
16
Hood Parts
Plastic Tie Wrap
Qty (2)
Screws for Metal Tray
Qty (2)
Parts Location
TOP
PANEL
CAULK
HERE
TOP
PANEL
INDOOR
COIL
ACCESS
PANEL

Advertisement

Table of Contents
loading