■Contact protection circuit for inductive loads
When an inductive load is connected, connect a diode (for commutation) in parallel with the load as necessary.
The diode (for commutation) must comply with the following specifications.
Standard
Reverse voltage
Forward current
Inductive load
Fuse
■Interlock
For loads such as forward/reverse contactors, etc., where a hazardous condition could result if switched ON simultaneously,
an external interlock should be provided for interlocking along with an interlock in the PLC program, as shown below.
Sink output type
+
Limit of forward
rotation
Limit of reverse
rotation
6 WIRING
94
6.6 Output Wiring
5 to 10 times as high as the load voltage
Load current or larger
Sink output type
Y
COM0
PLCs
-
Interlock
Forward rotation
Reverse rotation
PLC output
element
Inductive load
Y
Fuse
+V0
Source output type
-
Limit of forward
Interlock
rotation
Limit of reverse
rotation
Source output type
PLCs
+
Forward rotation
Reverse rotation
PLC output
element