Mitsubishi Electric FX5U User Manual page 95

Melsec iq-f
Hide thumbs Also See for FX5U:
Table of Contents

Advertisement

■Response time
Time taken from when the photocoupler of the module is driven (or shut off) to when the transistor is turned on (or off) differs
depending on the output terminal used. For specifications of each module, refer to the following.
For output specifications of the CPU module, refer to Page 21 Output Specifications.
For output specifications of the I/O modules, refer to Page 136 Output specifications.
The transistor OFF time is longer under lighter loads. For example, under a load of 24 V DC 40 mA, the
response time is approx. 0.3 ms.
When response performance is required under light loads, provide a dummy resistor as shown below to
increase the load current.
• Sink output type
Fuse
Load
■Output current
Maximum load differs for each module. For specifications of each module, refer to the following.
For output specifications of the CPU module, refer to Page 21 Output Specifications.
For output specifications of the I/O modules, refer to Page 136 Output specifications.
When driving a semiconductor device, carefully check the input voltage characteristics of the device.
■Open circuit leakage current
0.1 mA or less
Wiring precautions
■Protection circuit for load short-circuiting
A short-circuit at a load connected to an output terminal could cause burnout at the output device or the PCB.
To prevent this, a protection fuse should be inserted at the output. Use a load power supply capacity that is at least 2
times larger than the load current.
Load
Fuse
PLCs
Dummy
resistor
Y
COM0
Sink output type
Y
COM0
PLCs
• Source output type
Dummy
Fuse
Load
resistor
Source output type
Load
Y
Fuse
+V0
PLCs
Y
+V0
PLCs
6 WIRING
93
6.6 Output Wiring
6

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents