Mitsubishi Electric FX5U User Manual page 57

Melsec iq-f
Hide thumbs Also See for FX5U:
Table of Contents

Advertisement

Check of limitation on the number of input/output points
Check if the number of input/output points of the sample system configuration is within the limit range.
■Number of input/output points
(Page 46 Calculation of number of input/output points)
Type
CPU module
Expansion board
Expansion adapter
Expansion adapter
Input module
Output module
Output module
Output module
Simple motion module
Bus conversion module
Pulse output module
Analog input module
Temperature controller module
AnyWireASLINK master module
CC-Link intelligent device module
Number of
Number of occupied
input/output points
input/output points
+
96 points
■Number of remote I/O points
(Page 46 Calculation of number of remote I/O points)
Network
AnyWireASLINK
Remote I/O points
≤ 384 points
64 points
■Total number of I/O points and remote I/O points
(Page 45 Limitation on the Number of Input/Output Points)
Total number of input/output points
Number of input/output points
152 points
Model
FX5-32MR/ES
FX5-232-BD
FX5-232ADP
FX5-485ADP
FX5-16EX/ES
FX5-16EYT/ES
FX5-16EYT/ES
FX5-16EYR/ES
FX5-40SSC-S
FX5-CNV-BUS
FX3U-1PG
FX3U-4AD
FX3U-4LC
FX3U-128ASL-M
FX3U-64CCL
Number of input/output points
Calculation result
=
56 points
152 points
No. of remote I/O points
64 points
Maximum number of
Remote I/O points
OK
Remote I/O points
+
64 points
No. of input/output
points
32 points
16 points
16 points
16 points
16 points
Max. number of
input/output points
256 points
Calculation
result
input/output points
= 216 points
512 points
4.5 Rules of System Configuration and Examples of Reconfiguration
No. of occupied input/
output points
8 points
8 points
8 points
8 points
8 points
8 points
8 points
OK
Max. number of
OK
4 SYSTEM CONFIGURATION
4
55

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents