Toshiba RAV-SP1100UT-E Service Manual page 73

Hide thumbs Also See for RAV-SP1100UT-E:
Table of Contents

Advertisement

11-1-4. Monitor Function of Remote Controller Switch
n Call of sensor temperature display
<Contents>
Each sensor temperature of the remote controller,
indoor unit, and outdoor unit can become known by
calling the service monitor mode from the remote
controller.
<Procedure>
1
Push
+
buttons simultaneously for 4
seconds or more to call the service monitor
mode.
The service monitor goes on, the master indoor
unit No. is displayed, and then temperature of the
00
item code
is displayed.
2
Push the temperature setup
buttons to select the sensor No. (Item code)
of the sensor to be monitored.
The sensor numbers are described below:
Item code
00
01
Indoor
02
unit data
03
04
*1 Only master unit in group control
3
The temperature of indoor units and outdoor unit in a group control can be monitored by pushing
button to select the indoor unit to be monitored.
4
Pushing
button returns the display to usual display.
/
Data name
Room temp (under control) *1
Room temp (remote controller)
Indoor suction temp
Indoor coil temp (TCJ)
Indoor coil temp (TC)
4
<Operation procedure>
1
Item code
60
61
Outdoor
62
unit data
63
64
65
73
SET DATA
UNIT No.
R.C.
No.
UNIT
SET
CL
1
3
2
3
4
Returned to usual display
Data name
Heat exchanger temp TE
Outside temp TO
Discharge temp TD
Suction temp TS
Heat sink temp THS
2