Toshiba RAV-SP1100UT-E Service Manual page 115

Hide thumbs Also See for RAV-SP1100UT-E:
Table of Contents

Advertisement

Appendix
2. Required tools for installation work
No.
Part name
1
Plus screwdriver
2
Wrench
3
Motor drill
4
Faston crimping tool
5
Close-end connector
crimping tool
6
Cutting plier
7
Stripper
8
Cutter knife
9
Insulation tape
3. Cord heater installation wiring diagram
L
* Be sure to connect the fuse and the thermostat to LIVE side of the cord heater.
Outdoor unit
NOTE:
Separate the cord heater power from the air conditioner power, and connect it to its exclusive breaker.
By doing so, the power consumption can be decreased because the breaker can be turned off if there is no
possibility of freezing of the base in cooling operation, etc.
When the cord heater power is connected to the inverter P .C. board assembly or others without connected to the
exclusive breaker, the control P .C. board of the inverter assembly may cause a failure.
Specifications
It is used for disassembling and assembling of each cabinet.
It is used for disassembling and assembling of compressor fixing nuts.
Drill diameter:
It is used to make the additional holes on the base or the back cabinet.
Ø3.2 and Ø5.0
Fixing jig for #250
Fuse
Thermostat
Earth leakage circuit breaker
Earth leakage circuit breaker
Appendix-2
Usage
Cord heater
Power supply for air conditioner
Power supply for cord heater
N

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rav-sp560at-eRav-sp1400at-eRav-sp1100at-eRav-sp800at-e

Table of Contents