Starting The Parallel System In Normal Mode - Huawei UPS2000-G-6KRTS User Manual

Hide thumbs Also See for UPS2000-G-6KRTS:
Table of Contents

Advertisement

UPS2000-G-(6 kVA-20 kVA)
User Manual

Starting the Parallel System in Normal Mode

Perform the following steps to start the parallel system for the system to work in normal
mode.
Step 1 Close the external battery circuit breakers (if there are), or connect battery cables.
Step 2 Close the following circuit breakers in sequence: UPS mains input circuit breakers K
K
2, general mains input circuit breaker K
m
general bypass input circuit breaker K
The initialization screen is displayed. The parallel system supplies no power.
Step 3 Perform the following operations on each UPS:
Issue 10 (2017-01-19)
If a parallel system shares a battery string, set the same battery string capacity and charge
current for each UPS.
Before you start the parallel system, ensure that UPS output circuit breakers are both ON.
Check that parallel parameters have been synchronized. For the parallel parameters to be
synchronized, see appendix
In a 4+0 parallel system, the four parallel cables must be of the same length (1 meter or
longer), and connect to a remote junction box.
In the parallel system that uses the TN-C power distribution system, install four magnetic
rings on the PE cable on each UPS, bind the four magnetic rings together using binding
tape, and secure them in the nearest place. For the magnetic ring specifications, see
2-2.
Before starting a parallel system, ensure that all circuit breakers on the output side are OFF,
and do not start loads.
To prevent triggering overload protection, start the loads with higher power and then loads
with lower power.
Perform
Step 2
when there are two mains inputs. In the case of one mains input, you need only to
close the UPS mains input circuit breakers and general mains input circuit breaker.
If a PDU is configured, close the following circuit breakers: general mains input circuit breaker,
general bypass input circuit breaker, mains input circuit breakers for all UPSs on the PDU, bypass
input circuit breakers, and output circuit breakers for all UPSs on the PDU. The initiation screen is
displayed.
Initial startup
a.
Setting parameters on the Settings wizard screen
When the initialization is complete, the Settings wizard screen is displayed. Set the
language, system parameters, and battery parameters, and press
screen is displayed.
b.
Settings for transferring from single mode (preset) to parallel mode
On the standby screen, press
Parameters > Parallel > Single/Parallel to transfer from single mode to parallel
mode. Press ESC to return to the standby screen.
Non-initial startup
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
A Parallel Parameter
List.
, bypass input circuit breakers K
m
, and UPS AC output circuit breakers Q1 and Q2.
b
. Choose Main Menu > Settings > System
5 Operations
Table
1 and
m
1 and K
2,
b
b
. The standby
79