Troubleshooting - Huawei UPS2000-G-6KRTS User Manual

Hide thumbs Also See for UPS2000-G-6KRTS:
Table of Contents

Advertisement

UPS2000-G-(6 kVA-20 kVA)
User Manual
When a UPS is faulty, alarm information is displayed on the LCD. Critical alarms must be
processed before the UPS is powered on again. Otherwise, the fault may be extended, or the
UPS may be damaged.
Table 8-1
Table 8-1 Solutions to common faults
No.
1
2
3
4
Issue 10 (2017-01-19)
lists the solutions to common faults.
Symptom
The mains switch is ON.
The LCD does not display
anything. The system
does not perform
self-tests.
The mains is normal, but
the AC input indicator is
off. The UPS runs in
battery mode.
The UPS does not report
faults, but has no output
voltage.
The UPS does not start
after you press
.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
8

Troubleshooting

Possible Cause
Measure
The input power
Check the input power cable
supply is not
connection.
connected.
The input voltage
Use a multimeter to check that the
exceeds the limit.
UPS input voltage meets
specifications.
The mains switch
Turn on the mains switch.
is OFF.
The input power
Check the input power cable
cable is not
connection.
securely
connected.
The output
Check the output power cable
power cable is
connection.
not securely
connected.
is not
Press
pressed long
seconds until you hear a beep
enough.
sound.
8 Troubleshooting
for more than 5
91