Appearance - Huawei UPS2000-G-6KRTS User Manual

Hide thumbs Also See for UPS2000-G-6KRTS:
Table of Contents

Advertisement

UPS2000-G-(6 kVA-20 kVA)
User Manual

2.3 Appearance

Figure 2-3
front and rear views of the UPS2000-G-10 kVA.
the UPS2000-G-15 kVA/20 kVA.
Issue 10 (2017-01-19)
When the mains is normal, the rectifier boosts the mains input voltage and converts the
AC power into stable DC power for the inverter, and the mains charges batteries over a
charger. Then the inverter converts the DC power into stable AC power, which is
supplied to loads.
Battery mode
When the mains is abnormal or disconnected, the DC-DC step-up transformer boosts the
DC power supplied from batteries. Then the inverter converts the DC power into stable
AC power for powering loads.
Bypass mode
The mains supplies power directly to loads after filtering. The UPS transfers to bypass
mode when overload, overtemperature, or faults occur. This mode does not provide
battery backup capability.
Economy control operation (ECO) mode
If the bypass voltage and frequency are in the specified range, the UPS supplies power to
loads over the bypass. If the bypass voltage and frequency are outside the range, the UPS
transfers to normal or battery mode. ECO is short for economy control operation.
The UPS2000-G-15 kVA/20 kVA supports battery ECO mode only in the case of two mains inputs.
In battery ECO mode, the bypass supplies power to the UPS, and batteries are used as backup power.
If the bypass is abnormal, the UPS transfers to battery mode.
By default, ECO mode described in this document refers to mains ECO mode.
shows the front and rear views of the UPS2000-G-6 kVA.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
2 UPS2000-G-(6kVA-20kVA) Quick Introduction
Figure 2-5
shows the front and rear views of
Figure 2-4
shows the
14

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents