Outdoor Heat Exchanger Temperature Sensor(Outlet) Error - Fujitsu AB*A30LBT Service Instruction

Large ceiling type inverter
Table of Contents

Advertisement

Trouble shooting 5
OUTDOOR UNIT Error Method:
Outdoor Heat Exchanger Temperature
Sensor (Outlet) Error
Detective Actuators:
Outdoor Unit Main PCB Circuit
Heat Exchanger Temperature
Thermistor (Outlet)
Forecast of Cause :
1. Connector connection failure
Check Point 1 : Check connection of Connector
Check if connector is removed.
Check erroneous connection.
Check if thermistor cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
OK
OK
Check Point 2 : Remove connector and check Thermistor resistance value
Check Point 2 :
Thermistor Characteristics (Approx. value)
Temperature
Resistance Value (k )
Temperature
Resistance Value (k )
If Thermistor is either open or shorted, replace it and reset the power.
OK
OK
Check Point 3 :
Check Point 3 : Check voltage of Main PCB (DC5.0V)
Make sure circuit diagram of outdoor unit and check terminal voltage at Thermistor (DC5.0V)
3 2 1
3 2 1
3 2 1
3 2 1
CN64
CN62
If the voltage does not appear, replace Main PCB.
Indicate or Display:
Indoor Unit : Operation LED: 3 times blink, Timer LED: 3 times blink,
Outdoor Unit : LED 0.1sec ON/ 0.1sec OFF
ERROR CODE : E : 06
Detective details:
When Heat Exchanger Temperature Thermistor (Outlet) open or
short-circuit is detected at power ON or while running the compressor.
2.Thermistor failure
-10°C
-5°C
0°C
5°C
27.8
21.0
16.1
12.4
35°C
40°C
45°C
50°C
3.11
2.53
2.08
1.71
3 2 1
3 2 1
3 2 1
3 2 1
CN65
CN63
Filter LED
: OFF
3. Main PCB failure
10°C
15°C
20°C
9.63
7.56
5.98
60°C
70°C
80°C
1.19
0.840
0.606
07-09
25°C
30°C
4.77
3.84
90°C
100°C
0.446
0.333
DC