Room Temperature Sensor Error - Fujitsu AB*A30LBT Service Instruction

Large ceiling type inverter
Table of Contents

Advertisement

Trouble shooting 3
INDOOR UNIT Error Method:

Room Temperature Sensor Error

Detective Actuators:
Indoor Unit Controller PCB Circuit
Room Temperature Thermistor
Forecast of Cause :
1. Connector connection failure
Check Point 1 : Check connection of Connector
Check if connector is removed.
Check erroneous connection.
Check if thermistor cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
OK
Check Point 2 :
Check Point 2 : Remove connector and check Thermistor resistance value
Thermistor Characteristics (Approx. value)
Temperature
Resistance Value (k )
Temperature
Resistance Value (k )
If Thermistor is either open or shorted, replace it and reset the power.
OK
Check Point 3 : Check voltage of Controller PCB (DC5.0V)
Check Point 3 :
Make sure circuit diagram of indoor unit and check terminal voltage at Thermistor (DC5.0V)
GRAY
1 1
GRAY
2 2
1 2
1 2
1 2
1 2
1 2
CN5 CN7 CN8
If the voltage does not appear, replace Controller PCB.
Indicate or Display:
Indoor Unit : Operation LED: 2 times blink, Timer LED: 2 times blink,
Outdoor Unit
ERROR CODE : E : 02
Detective details:
When Room Temperature Thermistor open or short-circuit is
detected at power ON.
2.Thermistor failure
0°C
5°C
10°C
33.6
25.9
20.2
40°C
45°C
50°C
5.30
4.35
3.59
THERMISTOR
(PIPE TEMP.)
THERMISTOR
(ROOM TEMP.)
Filter LED
: OFF
: No indication
3. Controller PCB failure
15°C
20°C
25°C
15.8
12.5
10.0
07-07
30°C
35°C
8.04
6.51

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents