Pfc Circuit Error - Fujitsu AB*A30LBT Service Instruction

Large ceiling type inverter
Table of Contents

Advertisement

Trouble shooting 23
OUTDOOR UNIT Error Method:

PFC circuit error

Detective Actuators:
Outdoor Unit Main PCB Circuit
Forecast of Cause :
1. External cause
Check Point 1 : Check external cause at Indoor and Outdoor (Voltage drop or Noise)
Instant drop : Check if there is a large load electric apparatus in the same circuit.
Momentary power failure : Check if there is a defective contact or leak current
Noise : Check if there is any equipment causing harmonic wave near electric line.
(Neon bulb or electric equipment that may cause harmonic wave)
Check the complete insulation of grounding.
OK
OK
Check Point 2 : Check connection of Connector
Check if connector is removed.
Check erroneous connection.
Check if cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
OK
OK
Check Point 3 : Replace Main PCB
If Check Point 1, 2 do not improve the symptom, change Main PCB.
Indicate or Display:
Indoor Unit : Operation LED: 8 times blink, Timer LED: 4 times blink,
Outdoor Unit
ERROR CODE : E : 25
Detective details:
When inverter output DC voltage is higher than 425V for over 3 seconds,
the compressor stops.
If the same operation is repeated 5 times, the compressor stops permanently.
2. Connector connection failure
in the power supply circuit.
Filter LED
: OFF
: No indication
3. Main PCB failure
07-25