2-22. E: 73. Heat exchanger (Middle/Outlet) temperature
thermistor error (Outdoor unit)
Wired remote
Indicator
controller
Heat exchanger liquid temperature
thermistor
Detective actuator
Heat exchanger middle
temperature thermistor
Forecast of cause
Check Point 1 : Check the connector connection and cable open
Connector connection state check
Cable open check
Check Point 2 : Check the thermistor
For the outdoor unit heat exchanger thermistor resistance value, refer to
mistor resistance values"
If thermistor is either open or shorted, replace it and reset the power.
Check point 3. Check voltage of main PCB
Make sure circuit diagram of outdoor unit and check terminal voltage at thermistor
(DC 5.0 V).
NOTE: For details of thermistor connector, refer to
TECHNICAL DATA AND PARTS LIST on page 02-33.
If the voltage does not appear, replace main PCB.
2-22. E: 73. Heat exchanger (Middle/Outlet) temperature thermistor error (Outdoor
unit)
Error code
on page 03-60.
"Wiring diagrams"
End
- (03-26) -
E: 73
Heat exchanger liquid temperature thermistor short
or open detected
Heat exchanger middle temperature thermistor
short or open detected
Connector failure
Thermistor failure
Main PCB failure
"Ther-
in Chapter 2.
2. Troubleshooting with error code