Trouble shooting 22
OUTDOOR UNIT Error Method:
Excessive high pressure protection
Detective Actuators:
Outdoor Unit Main PCB Circuit
Outdoor Fan Motor
Heat Exchanger Temp. Thermistor
Outdoor unit Electronic Expansion Valve
Forecast of Cause :
1. Defective connection of electric components 2. Outdoor Fan Operation failure
3. Outdoor Heat Exchanger clogged
Check Point 1 : Check connections of Outdoor Unit Electrical Components
Check if
the terminal connection
Check if connector is removed.
Check erroneous connection.
Check if cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
OK
Check Point 2 : Check Outdoor Fan, Heat Exchanger
Is there anything obstructing the air distribution circuit?
Is there any clogging of Outdoor Heat Exchanger?
Is the Fan rotating by hand when operation is off ?
>> If the Fan Motor is locked, replace it.
OK
Check Point 3 : Check Outdoor Fan
Check Outdoor Fan Motor. (Refer to Trouble shooting 19)
>> If the Fan Motor is failure, replace it.
OK
OK
Check Point 4 : Check Thermistor
Check Thermistor. (Refer to Trouble shooting 5)
>> If the Thermistor is failure, replace it.
OK
OK
Check Point 5 : Check Electronic Expansion Valve
Check EEV.
(PARTS INFORMATION 4)
OK
OK
Check Point 6 : Replace Main PCB
If Check Point 1
5 do not improve the symptom, change Main PCB.
Indicate or Display:
Indoor Unit : Operation LED: 7 times blink, Timer LED: 3 times blink,
Outdoor Unit
on cooling
ERROR CODE : E : 24
Detective details:
Excessive high pressure protection on cooling mode has been
activated.
4. Thermistor failure
is loose.
Filter LED
: OFF
: No indication
5. EEV failure
07-24
6. Main PCB failure