Outdoor Heat Exchanger Temperature Sensor(Outlet) Error - Fujitsu AB A30LBT Series Service Instruction

Hide thumbs Also See for AB A30LBT Series:
Table of Contents

Advertisement

Trouble shooting 5
OUTDOOR UNIT Error Method:
Outdoor Heat Exchanger Temperature
Sensor (Outlet) Error
Detective Actuators:
Outdoor Unit Main PCB Circuit
Heat Exchanger Temperature
Thermistor (Outlet)
Forecast of Cause:
1. Connector connection failure 2.Thermistor failure 3. Main PCB failure
Check Point 1 : Check connection of Connector
Check if connector is removed.
Check erroneous connection.
Check if thermistor cable is open.
>> Upon correcting the removed connector or mis-wiring, reset the power.
OK
Check Point 2 : Remove connector and check Thermistor resistance value
Thermistor Characteristics (Approx. value)
Temperature
(°C )
Resistance Value (k )
Temperature
(°C )
Resistance Value (k )
If Thermistor is either open or shorted, replace it and reset the power.
OK
Check Point 3 : Check voltage of Main PCB (DC5.0V)
Make sure circuit diagram of outdoor unit and check terminal voltage at Thermistor (DC5.0V)
BROWN
1
1
CN 64
2
2
BROWN
3
3
BLUE
1
1
CN 62
2
2
BLUE
3
3
BROWN
1
1
CN 63
2
2
BROWN
3
3
BLACK
1
1
CN 65
2
2
BLACK
3
3
If the voltage does not appear, replace Main PCB.
Indicate or Display:
Refer to error code table.
Detective details:
When Heat Exchanger Temperature Thermistor (Outlet) open or
short-circuit is detected at power ON or while running the compressor.
-10
-5
0
27.8
21.0
16.1
35
40
45
3.11
2.53
2.08
THERMISTOR
( COMPRESSOR TEMP. )
THERMISTOR
( OUTDOOR TEMP. )
THERMISTOR
( DISCHARGE PIPE )
THERMISTOR
( HEAT EXCHANGER )
02-09
5
10
15
12.4
9.63
7.56
50
60
70
1.71
1.19
0.84
20
25
30
5.98
4.77
3.84
80
90
100
0.60
0.45
0.33