6 Connection and Commissioning
Pin group
Analog current input 2
Analog current input 3
Procedure:
1. Connect the connection cable to the sensor (see the manual from manufacturer). Trim the
unneeded insulated conductors up to the cable shield and note down the conductor colors.
2. For connection to the pin group Analog current input 1, perform the following steps:
• Unlock conductor entry 4 with a screwdriver and insert the insulated conductor of the
wire into the conductor entry.
• Unlock conductor entries 2 and 3 with a screwdriver and insert the insulated conductors
of the connection cable into the conductor entries. Observe the pin assignment.
• Insert the eight-pole plug into pin row A in terminal X8.
3. For connection to the pin group Analog current input 2, perform the following steps:
• Unlock conductor entry 8 with a screwdriver and insert the insulated conductor of the
wire into the conductor entry.
• Unlock conductor entries 6 and 7 with a screwdriver and insert the insulated conductors
of the connection cable into the conductor entries. Observe the pin assignment.
• Insert the eight-pole plug into pin row A in terminal X8.
4. For connection to the pin group Analog current input 3, perform the following steps:
• Unlock conductor entry 4 with a screwdriver and insert the insulated conductor of the
wire into the conductor entry.
• Unlock conductor entries 2 and 3 with a screwdriver and insert the insulated conductors
of the connection cable into the conductor entries. Observe the pin assignment.
• Insert the eight-pole plug into pin row B in terminal X8.
5. On the connection cable, mark the terminal and the pin row to which the connection cable is
assigned. Use the supplied cable tie with caption field.
6. Write down the terminal assignment on the supplied supplementary sheet.
Connecting a Sensor to the Analog Voltage Input
Additionally required material (not included in the scope of delivery):
☐ 1 sensor
☐ 1 connection cable (see Section 6.3 "Cable Requirements", page 28)
46
ClusterController-IA-en-15
Pin
Signal
A5
Not assigned
A6
I+
A7
I−
A8
GND
B1
Not assigned
B2
I+
B3
I−
B4
GND
SMA Solar Technology AG
Explanation
Reserved for future applications
Current input
Current return
Shield ground
Reserved for future applications
Current input
Current return
Shield ground
Installation Manual