4 Product Description
Configuring device parameters
You can configure specific parameters of individual devices or entire device classes via the user
interface of the Cluster Controller. You must be logged into the user group Installer on the
Cluster Controller. The device parameters that can be configured, if any, depend on the device and
the rights of the user group. You may only change grid-sensitive device parameters
(SMA Grid Guard parameters) with the approval of the grid operator and using your personal
SMA Grid Guard code.
Sending e-mail alarms in the event of critical system statuses
You have the option of receiving prompt information on critical system statuses via e-mail. The
Cluster Controller automatically sends a notification if alarm-related events occur in the system.
Feedback on current total active power of the system
You have the option of being informed of the total active power currently generated by the system
via an analog current output signal.
Implementation and feedback of grid operator setpoints for active power
limitation and reactive power operation under grid management services
With the Cluster Controller, as part of grid management services you can implement different grid
operator setpoints for active power limitation and reactive power operation of your system. The
Cluster Controller can implement the setpoints using open-loop control or closed-loop control.
For Cluster Controller systems without self-consumption and with direct limitation of active power
feed-in, the operating mode Open-loop control is used. In this operating mode, the
Cluster Controller can receive the setpoints either in the form of digital or analog signals, or via
Modbus. The different types of signal source can be combined so that, for example, the setpoints
for the active power limitation are received as digital signals and the reactive power setpoints are
received as analog signals: For Cluster Controller systems with self-consumption, the operating
mode Closed-loop control is used. In this operating mode, you can regulate the active power fed
in by the system at the grid-connection point and limit it e.g. to a fixed percentage value. In
agreement with your grid operator, you can use the user interface of the Cluster Controller to
configure which setpoints of the Cluster Controller are to be transmitted to the connected inverters
depending on the respective signal. In addition, you can use a digital response contact or an
analog current output signal to inform the grid operator of the setpoints (if any) for active power
limitation and reactive power operation that are currently being used in the system.
Implementation and feedback of setpoints for active power limitation when PV
electricity is directly marketed
The PV current generated by your system can be directly marketed. The Cluster Controller can
receive setpoints for active power limitation from the direct marketer as digital or analog signals or
via Modbus. The "CLCON-S-10" model provides a Modbus register for sending setpoints via
Modbus. The model "CLCON-10" provides two Modbus registers.
The Cluster Controller can provide feedback about the current feed-in power of the system to the
direct marketer via digital or analog signals. To avoid conflicts when different setpoints are used by
the grid operator and the direct marketer, the Cluster Controller always implements the setpoint that
more strongly limits the active power of the system.