7 COMMUNICATIONS
Table 7–1: 239 MEMORY MAP (Sheet 12 of 18)
REG
GROUP
ADDR
(HEX)
109D
109E
109F
10A0
RTD 1
10A1
10A2
10A3
10A4
10A5
10A6
10A7
10A8
RTD 2
10A9
10AA
10AB
10AC
10AD
10AE
10AF
10B0
RTD 3
10B1
10B2
10B3
7
10B4
10B5
10B6
10B7
10B8
RTD SENSOR
10B9
10BA
10BB
10BC
10BD
10BE
10BF
1, 2, 3,
,
,
,
, †, ‡
*
**
***
****
See page 7–30 for explanation of Table notes.
7-24
Courtesy of NationalSwitchgear.com
DESCRIPTION
Reserved
Reserved
Reserved
RTD 1 Application (RTD Option)
RTD 1 Type (RTD Option)
RTD 1 Trip Temp. (RTD Option)
RTD 1 Trip Temp. (RTD Option)
RTD 1 Alarm Temp. (RTD Option)
RTD 1 Alarm Temp. (RTD Option)
Reserved
Reserved
RTD 2 Application (RTD Option)
RTD 2 Type (RTD Option)
RTD 2 Trip Temp. (RTD Option)
RTD 2 Trip Temp. (RTD Option)
RTD 2 Alarm Temp. (RTD Option)
RTD 2 Alarm Temp. (RTD Option)
Reserved
Reserved
RTD 3 Application (RTD Option)
RTD 3 Type (RTD Option)
RTD 3 Trip Temp. (RTD Option)
RTD 3 Trip Temp. (RTD Option)
RTD 3 Alarm Temp. (RTD Option)
RTD 3 Alarm Temp. (RTD Option)
Reserved
Reserved
RTD Sensor Fail Alarm (RTD Option)
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
239 Motor Protection Relay
7 COMMUNICATIONS
REGISTER
STEP
UNITS &
VALUE
VALUE
SCALE
RANGE
0-2
1
---
0-3
1
---
0 - 201
1
°C
0 - 401
1
°F
0 - 201
1
°C
0 - 401
1
°F
0-2
1
---
0-3
1
---
0 - 201
1
°C
0 - 401
1
°F
0 - 201
1
°C
0 - 401
1
°F
0-2
1
---
0-3
1
---
0 - 201
1
°C
0 - 401
1
°F
0 - 201
1
°C
0 - 401
1
°F
0-1
1
---
FOR-
FACTORY
MAT
DEFAULT VALUE
(CONVERTED)
F24
1 = STATOR
F25
0 = 100 PT
F1 **
130 °C
F1 **
266 °F
F1 **
110 °C
F1 **
230 °F
F24
2 = BEARING
F25
0 = 100 PT
F1 **
90 °C
F1 **
194 °F
F1 **
75 °C
F1 **
167 °F
F24
2 = BEARING
F25
0 = 100 PT
F1 **
90 °C
F1 **
194 °F
F1 **
75 °C
F1 **
167 °F
F20
0 = OFF
GE Multilin