GE 239 Instruction Manual page 56

Multilin motor protection relay
Hide thumbs Also See for 239:
Table of Contents

Advertisement

4 PROGRAMMING
SEE PREVIOUS PAGE
4
SEE NEXT PAGE
4-18
Courtesy of NationalSwitchgear.com
SEE PREVIOUS PAGE
| RTD 1
|
RTD 1 APPLICATION:
STATOR
RTD 1 TYPE:
100 PT
RTD 1 TRIP
MESSAGE
TEMPERATURE ≥ 130 °C
MESSAGE
RTD 1 ALARM
TEMPERATURE ≥ 110 °C
| RTD 2
|
RTD 2 APPLICATION:
STATOR
RTD 2 TYPE:
100 PT
MESSAGE
RTD 2 TRIP
TEMPERATURE ≥ 90 °C
MESSAGE
RTD 2 ALARM
TEMPERATURE ≥ 75 °C
| RTD 3
|
RTD 3 APPLICATION:
BEARING
RTD 3 TYPE:
100 PT
RTD 3 TRIP
TEMPERATURE ≥ 90 °C
MESSAGE
RTD 3 ALARM
MESSAGE
TEMPERATURE ≥ 75 °C
| RTD SENSOR FAILURE
|
RTD SENSOR FAILURE
ALARM: OFF
MESSAGE
MESSAGE
SEE NEXT PAGE
239 Motor Protection Relay
4 PROGRAMMING
Range: STATOR, BEARING, OFF
Range: 100PT, 100NI, 120NI, 10CU
Range:
0 to 200°C, OFF; step 1°C
0 to 400°F, OFF; step 1°F
Range:
0 to 200°C, OFF; step 1°C
0 to 400°F, OFF; step 1°F
Range: STATOR, BEARING, OFF
Range: 100PT, 100NI, 120NI, 10CU
Range:
0 to 200°C, OFF; step 1°C
0 to 400°F, OFF; step 1°F
Range:
0 to 200°C, OFF; step 1°C
0 to 400°F, OFF; step 1°F
Range: STATOR, BEARING, OFF
Range: 100PT, 100NI, 120NI, 10CU
Range:
0 to 200°C, OFF; step 1°C
0 to 400°F, OFF; step 1°F
Range:
0 to 200°C, OFF; step 1°C
0 to 400°F, OFF; step 1°F
Range: ON, OFF
DESIGNATES SETPOINTS
THAT ARE ONLY VISIBLE IF
RTD OPTION IS INSTALLED
GE Multilin