Anybus Modbus to BACnet Gateway User Manual page 49

Table of Contents

Advertisement

Appendix C: BACnet Objects
Analog Value Object Type (continued)
Property Identifier
High_Limit
Low_Limit
Deadband
Limit_Enable
Event_Enable
Acked_Transitions
Notify_Type
Event_Time_Stamps
Profile_Name
* Only available when specific object has a Notification Class configured
Binary Input Object Type
Property Identifier
Object_Identifier
Object_Name
Object_Type
Present_Value
Description
Device_Type
Status_Flags
Event_State
Reliability
Out_Of_Service
Polarity
Inactive_Text
Active_Text
Change_Of_State_Time
Change_Of_State_Count
Time_Of_State_Count_Reset
Elapsed_Active_Time
Time_Of_Active_Time_Reset
Time_Delay
Notification_Class
Alarm_Value
Event_Enable
Acked_Transitions
Notify_Type
Event_Time_Stamps
Profile_Name
* Only available when specific object has a Notification Class configured
Modbus to BACnet Gateway User Manual
Property Datatype
REAL
REAL
REAL
BACnetLimitEnable
BACnetEventTransitionBits
BACnetEventTransitionBits
BACnetNotifyType
BACnetArray[N] of
BACnetTimeStamp
CharacterString
Property Datatype
BACnetObjectIdentifier
CharacterString
BACnetObjectType
BACnetBinaryPV
CharacterString
CharacterString
BACnetStatusFlags
BACnetEventState
BACnetReliability
BOOLEAN
BACnetPolarity
CharacterString
CharacterString
BACnetDatetime
Unsigned
BACnetDatetime
Unsigned
BACnetDatetime
Unsigned
Unsigned
BACnetBinaryPV
BACnetEventTransitionBits
BACnetEventTransitionBits
BACnetNotifyType
BACnetArray[N] of
BACnetTimeStamp
CharacterString
Value
-
-
-
-
-
-
-
-
-
Value
(Binary Input, 0)
Configurable through BACnet
and Config Tool
BINARY_INPUT (3)
INACTIVE (0) / ACTIVE (1)
-
-
{FALSE, FALSE/TRUE, FALSE,
FALSE}
STATE_NORMAL (0)
NO_FAULT_DETECTED (0),
UNRELIABLE_OTHER (7)
FALSE
NORMAL (0)
Configurable through BACnet
and Config Tool
Configurable through BACnet
and Config Tool
-
-
-
-
-
-
-
-
-
-
-
-
-
47 (56)
ASHRAE
Anybus
O
R*
O
R*
O
R*
O
R*
O
R*
O
R*
O
R*
O
R*
-
O
ASHRAE
Anybus
R
R
R
R
R
R
R
R
-
O
-
O
R
R
R
R
O
R
R
R
R
R
O
R
O
R
O
R
O
R
O
R
O
R
O
R
O
R*
O
R*
O
R*
O
R*
O
R*
O
R*
O
R*
-
O