3. Mounting the Temperature Sensors

3.1. Installation in temperature pocket
Place the O-ring in the middle
-
groove.
screw nut up to the O-ring.
Holding the screw nut in
-
place, insert the sensor into
the ball valve and tighten the
screw nut.

3.2. Installation in a ball valve

Remove the blind cap or plug
-
and its gasket. Check that all
surfaces are clean.
Place the O-ring in the groove
-
closest to the tip of the
sensor.
screw nut up to the O-ring.
Holding the screw nut in
-
place, insert the sensor into
the ball valve and tighten the
screw nut.

4. Start of Operation

Slowly open the shut-off valves
-
Check for leakage and proper functioning
-
Clean the calculator
-
After confirming that the heat meter is functioning
properly, insert and tighten the sealing wires for
the temperature sensors and the heat meter itself.
When replacing a meter at the end of a verification
period note the meter readings and the serial
numbers of the old and new meters.
Please also check the following points:
Is the heat meter the appropriate size?
Is the heating system in operation?
Are the shut-off valves open?
Is the heating system clear (dirt filters not
clogged)?
Are the temperature sensors sealed with
wires (to avoid tampering)?
Is the directional arrow on the flow sensor
in the correct direction?
Is a flow volume displayed?
Is a plausible temperature difference dis-
played?
For instruments with two external temp-
erature sensors, is the forward flow sensor
(red) in the forward flow and the return flow
sensor (blue) in return flow pipe?
For instruments with a built-in return flow
temperature sensor, is the flow sensor
mounted in the return flow?
Installation and Operating Instructions V. 1.03 October'06
Slide
the
sealing
Slide
the
sealing
microCLIMA
Energy Meter microCLIMA

5. Technical Data

Type
Flow sensor
Nominal flow
Maximum flow
Nominal pressure
Low flow
horizontal
threshold
vertical
Temperature range
Mounting position
Calculator
Ambient temperature
Temperature range
Temperature difference
Power supply
Operating life
Data storage
Display
Interfaces
Temperature sensors
Type
Connection
Diameter
Cable length
6. The Display Set-up
The calculator has a liquid crystal display with 8
digits and special characters. The values that can
be shown are divided into three display loops.
main loop
technician's loop
statistics loop
All data is retrieved using the key next to the dis-
play. The standard display has been set to perma-
nently show the total heat quantity consumed since
the meter was put into operation.
At the start you are automatically in the main loop.
By pressing the key longer than 4 seconds you
change to the next loop. Keep the key pressed
until you reach the desired information loop.
To change the information display within a loop,
simply give a short press to the key. In this way,
you can scan all the information in the loop.
After one minute of non-use, the display returns to
the total heat quantity, the standard display.
0.6
1.5
2.5
3
m
/h
0.6
1.5
2.5
3
m
/h
1.2
3.0
5.0
bar
10
3.5
7
10
l/h
4
7
10
°C
15...90
any
°C
5...55
°C
1...130
K
3...100
3 V, Lithium
6 + 1
Years
(10 + 1 optional)
E²PROM, daily
8-digit
Infrared
M-bus (optional)
Pulse output
(optional)
Platinum precision
resistor
2-wire technique
mm
5.0 (optional 5.2)
m
1.5 (optional 3.0)
2