6. SOUND PRESSURE LEVELS
Measurement condition
PQRY-P144, 168, 192, 216, 240TSLMU-A/YSLMU-A
Sound level of PQRY-P144TSLMU-A/YSLMU-A
90
Stand 60Hz
Low
60Hz
80
70
60
50
40
30
Approximate minimum
20
audible limit on
continuous noise
10
63
125
250
500
Octave band central frequency (Hz)
63
125
250
Standard
60Hz
69.5 48.5 47.5 45.0 42.5
Low noise mode
60Hz
44.5 45.0 41.5 46.0 43.0
When Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operation
from Low noise mode automatically in the case that the operation condition is severe.
Sound level of PQRY-P168TSLMU-A/YSLMU-A
90
Stand 60Hz
Low
60Hz
80
70
60
50
40
30
Approximate minimum
20
audible limit on
continuous noise
10
63
125
250
500
Octave band central frequency (Hz)
63
125
250
Standard
60Hz
67.0 49.0 51.0 46.0 44.5
Low noise mode
60Hz
66.5 47.0 45.5 45.5 43.0
When Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operation
from Low noise mode automatically in the case that the operation condition is severe.
• •
Depending on the operation conditions, the unit generates noise caused by valve actuation, refrigerant flow, and pressure
changes when operating normally. Please consider to avoid location where quietness is required.
For BC controller, it is recommended to be installed in places such as ceilings of corridor, rest rooms and plant rooms.
WR2-48
3-1/4ft.
(1m)
Measurement
location
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
1k
2k
4k
8k
500
1k
2k
4k
8k
dB(A)
37.5
35.0
28.5
49.0
36.0
33.5
25.0
47.0
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
1k
2k
4k
8k
500
1k
2k
4k
8k
dB(A)
39.5
38.0
29.5
50.0
37.0
34.5
27.0
48.0
PQRY-P-T(S)LMU, Y(S)LMU (April 2017 Ver2)
Sound level of PQRY-P192TSLMU-A/YSLMU-A
90
Stand 60Hz
Low
60Hz
80
70
60
50
40
30
Approximate minimum
20
audible limit on
continuous noise
10
63
125
250
500
Octave band central frequency (Hz)
63
125
250
Standard
60Hz
59.5 49.0 53.0 47.0 45.5
Low noise mode
60Hz
69.5 48.5 47.5 45.0 42.5
When Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operation
from Low noise mode automatically in the case that the operation condition is severe.
Sound level of PQRY-P216TSLMU-A/YSLMU-A
90
Stand 60Hz
Low
60Hz
80
70
60
50
40
30
Approximate minimum
20
audible limit on
continuous noise
10
63
125
250
500
Octave band central frequency (Hz)
63
125
250
Standard
60Hz
57.5 63.0 57.5 49.0 47.5
Low noise mode
60Hz
68.0 49.5 47.0 46.0 44.0
When Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operation
from Low noise mode automatically in the case that the operation condition is severe.
Sound level of PQRY-P240TSLMU-A/YSLMU-A
90
Stand 60Hz
Low
60Hz
80
70
60
50
40
30
Approximate minimum
20
audible limit on
continuous noise
10
63
125
250
500
Octave band central frequency (Hz)
63
125
250
Standard
60Hz
54.0 66.0 59.5 50.0 48.5
Low noise mode
60Hz
66.0 50.0 46.0 47.0 45.0
When Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operation
from Low noise mode automatically in the case that the operation condition is severe.
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
1k
2k
4k
8k
500
1k
2k
4k
8k
dB(A)
40.5
40.0
30.5
51.0
37.5
35.0
28.5
49.0
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
1k
2k
4k
8k
500
1k
2k
4k
8k
dB(A)
43.5
45.0
36.0
55.0
39.5
36.0
29.5
49.5
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
1k
2k
4k
8k
500
1k
2k
4k
8k
dB(A)
45.5
47.0
38.5
57.0
40.5
37.0
30.0
50.0
© 2017 Mitsubishi Electric US, Inc.