11. M-NET CONTROL
11-4-3-10. TG-2000A(*1)+AE-200A/AE-50A/EW-50A
AE-200A can control max. 50 indoor units;
TG-2000A can control max. 40 AE-200A, AE-50A, and EW-50A;*2
TG-2000A can control max. 2000 indoor units.
AE-200A
000
CN21
BC controller
HUB
TB02
PC with
TG-2000A
AE-50A/
EW-50A
LAN
000
BC controller
53
TB02
BC controller
(Main)
92
TB02
*1 TG-2000A (Ver.6.5 or later) supports AE-200A/AE-50A (Ver.7.10 or later).
TG-2000A (Ver.6.60 or later) supports EW-50A.
*2 When AE-200A connected with AE-50A is connected, the number of AE-50A will be the maximum controllable number.
TG-2000A can control up to 40 AE-200A/AE-50A or AE-200A without AE-50A connection.
*3 For Wireless R/C and Signal receiver unit (SRU), channel 1, 2 and 3 are selectable and should be set to same channel.
© 2017 Mitsubishi Electric US, Inc.
<Two heat source units>
PQRY
OC
OS
TB7
TB7
51
CN40
CN41
CN40
DipSW5-1
DipSW5-1
ON
TB3
TB3
Group 1
Indoor unit
53
01
TB5
TB15
TB5
*3
SRU
*3
Wireless R/C
PQRY
OC
TB7
TB7
51
CN40
CN41
CN40
DipSW5-1
DipSW5-1
ON
TB3
TB3
Group 1
Group 2
Indoor unit
01
02
TB5
TB5
101
102
ME R/C
ME R/C
Group 31
Group 32
Indoor unit
41
42
TB5
TB5
141
142
ME R/C
ME R/C
PQRY-P-T(S)LMU, Y(S)LMU (April 2017 Ver2)
<One heat source unit>
PQRY
OC
TB7
52
51
CN41
CN40
CN41
DipSW5-1
ON
ON
TB3
Group 2
02
03
TB15
TB5
TB15
TB2
Transmission Booster
MA R/C
PQRY
OS
OC
TB7
52
91
CN41
CN40
CN41
DipSW5-1
ON
ON
TB3
03
TB5
TB2
Transmission Booster
PAC-SF46EPA
Group 33
BC controller
LOSSNAY
(Sub)
Interlocked with
M-NET address 42
94
43
TB02
TB5
Group 40
42
TB3
TB5
TB15
PAC-SF46EPA
MA R/C
MA R/C
(Main)
(Sub)
Group 21
30
TB3
TB5
130
180
ME R/C ME R/C
Group 34
Group 35
44
45
TB5
TB5
144
145
195
ME R/C
ME R/C ME R/C
WR2-135