10. ELECTRICAL WORK
Model
PCFY-P15NKMU-ER1
PCFY-P24NKMU-ER1
PCFY-P30NKMU-ER1
PCFY-P36NKMU-ER1
PKFY-P06NBMU-E2
PKFY-P08NHMU-E2
PKFY-P12NHMU-E2
PKFY-P15NHMU-E2
PKFY-P18NHMU-E2
PKFY-P24NKMU-E2.TH
PKFY-P30NKMU-E2.TH
PFFY-P06NEMU-E
PFFY-P08NEMU-E
PFFY-P12NEMU-E
PFFY-P15NEMU-E
PFFY-P18NEMU-E
PFFY-P24NEMU-E
PFFY-P06NRMU-E
PFFY-P08NRMU-E
PFFY-P12NRMU-E
PFFY-P15NRMU-E
PFFY-P18NRMU-E
PFFY-P24NRMU-E
PVFY-P12NAMU-E
PVFY-P18NAMU-E
PVFY-P24NAMU-E
PVFY-P30NAMU-E
PVFY-P36NAMU-E
PVFY-P48NAMU-E
PVFY-P54NAMU-E
PWFY-P36NMU-E-AU
PWFY-P72NMU-E-AU
© 2017 Mitsubishi Electric US, Inc.
Symbols: MCA : Min.Circuit Amps (=1.25xFLA) FLA : Full Load Amps
Indoor Unit
Hz
Volts
Voltage range
60Hz
208 / 230V
188 to 253V
60Hz
208 / 230V
198 to 253V
60Hz
208 / 230V
188 to 253V
60Hz
208 / 230V
188 to 253V
60Hz
208 / 230V
188 to 253V
60Hz
208 / 230V
188 to 253V
PQRY-P-T(S)LMU, Y(S)LMU (April 2017 Ver2)
IFM :Indoor Fan Motor
IFM
MCA(A)
FLA(A)
0.44 / 0.44
0.35 / 0.35
0.52 / 0.52
0.41 / 0.41
1.22 / 1.22
0.97 / 0.97
1.22 / 1.22
0.97 / 0.97
0.19 / 0.19
0.15 / 0.15
0.38 / 0.38
0.30 / 0.30
0.38 / 0.38
0.30 / 0.30
0.38 / 0.38
0.30 / 0.30
0.38 / 0.38
0.30 / 0.30
0.63 / 0.63
0.50 / 0.50
0.63 / 0.63
0.50 / 0.50
0.32 / 0.34
0.25 / 0.27
0.32 / 0.34
0.25 / 0.27
0.34 / 0.38
0.27 / 0.30
0.40 / 0.44
0.32 / 0.35
0.48 / 0.53
0.38 / 0.42
0.59 / 0.64
0.47 / 0.51
0.32 / 0.34
0.25 / 0.27
0.32 / 0.34
0.25 / 0.27
0.34 / 0.38
0.27 / 0.30
0.40 / 0.44
0.32 / 0.35
0.48 / 0.53
0.38 / 0.42
0.59 / 0.64
0.47 / 0.51
3.00 / 3.00
2.4 / 2.4
3.00 / 3.00
2.4 / 2.4
3.00 / 3.00
2.4 / 2.4
4.13 / 4.13
3.3 / 3.3
4.13 / 4.13
3.3 / 3.3
5.63 / 5.63
4.5 / 4.5
5.63 / 5.63
4.5 / 4.5
0.09
-
0.09
-
WR2-115