1. APPLICATION The N14 meter is a programmable digital panel instrument destined for the measurement of 3-phase, 3 or 4-wire power network parameters, in balanced or unbalanced systems with the simultaneous display of me- asured quantities and digital transmission of their values.
3. BASIC REQUIREMENTS AND OPERATIONAL SAFETY In the security scope, the meter meets the requirements of EN 61010-1 standard. Remarks concerning the operator safety: All operations concerning the meter installation and connections should be carried out by qualified skilled personnel and national regulations for the prevention of accidents must be observed.
Fig. 1. Overall meter dimensions 5. METER DESCRIPTION 5.1. Current inputs All current inputs are galvanically isolated (internal current transformers). The meter is adapted to co-operate with external measuring current transformers. Displayed current values and derived quantities are automatically re-counted by the quantity of the introduced external transformer ratio. Current inputs are defined in the order as 1 A or 5 A.
6.2. Messages after switching the supply on After switching the supply on, the meter carries out the display test and displays the name of the N14 meter with the current program version and rated values of voltages and cur- rents.
Page 13
6.3. Working modes Fig.6. Working modes of N14 meter...
Page 14
6.4. Parametr preview Quantities are displayed in the measurement mode acc. to the set- tled tables. The pressure of the push (left) or push (top) causes the transition between displayed quantities. The preview of 3-phase values: mean, minimal and maximal is acces- sible after pressing the acceptation (Enter) push.
6.5. Setting of parameters The entry in the programming mode is carried out by pressing and hol- ding during ca 3 sec. pushes. The entry in the programming mode is protected by the access code. In case when there is no code, the program transits into the programming option.
Page 16
Following values are set by means of pushes: Posi- tion of the decimal digit is selected by the push, the digit value is increased by the push. The active position is signalled by the cursor. The value is accepted by the push or abandoned by pres- sing the push.
Page 17
6.5.3. Setting of alarm parameters In options, select the mode A and confirm the choice by the push. Table 6 Parameter name Displayed information Default value Range of nor, on, oFF, 0...120 0...120 0...300 YES/no changes table 7 hon, hoF Selection of monitored quantity: Table 7 Item...
Page 18
Table 7 (continuation) apparent power of phase L2 Un x In [VA]* ac ve power factor of phase L2 voltage - phase L3 Un [V]* current in phase L3 In [A]* ac ve power of phase L3 Un x In x cos(0 ) [W]* reac ve power of phase L3 Un x In x sin(90...
Page 19
a) nor Aon > Aof b) nor c) On d) OFF Fig. 8. Alarm types: a),b) normal c) disabled d) enabled.
Register map of the N14 meter. In the N14 meter, data are placed in 16 and 32-bit registers. Process variables and meter parameters are placed in the address area of registers in the way dependent on the variable value type.
Page 21
7500 – 7566 Description of registers are included in the (32 bits) table 10. Registers for readout. * accessible from the program version 1.04 Table 9 Table of 16 – bit registers for N14 meter Register Operations Range Description Default...
Page 22
Table 9 4016 0..65535 Ac ve energy, two younger bytes* 4017 0..15258 Reac ve energy, two older bytes* 4018 0..65535 Reac ve energy, two younger bytes* 4019 0..65535 Status register - descrip on below* 4020 0..15258 Output ac ve energy, two older bytes* 4021 0..65535 Output ac ve energy, two younger bytes*...
Page 23
Table of 32 bit registers for N14 meter Table 10 16-bit 32-bit Description Register Unit Register address address 7000 7500 Voltage of phase L1 7002 7501 Current of phase L1 7004 7502 Active power of phase L1 7006 7503 Reactive power of phase L1...
Page 24
Table of 32 bit registers for N14 meter Table 10 7064 7532 Mean phase-to-phase voltage 7066 7533 Mean 15-minute active power 7068 7534 Reserved 7070 7535 Reserved 7072 7536 Mean minimal 3-phase voltage 7074 7537 Mean maximal 3-phase voltage 7076...
Page 25
3-phase reac ve induc ve energy (number of 7116 7558 the register 7559 overfi lls, zeroed a er exceeding 99999999.9 kVarh)* 3-phase reac ve induc ve energy (counter 7118 7559 to ng to 99999.9 kVarh)* 3-phase reac ve induc ve energy (number of the 7120 7560 MVarh...
8. ERROR CODES Messages about errors can appear during the meter operation. Reasons of these errors are presented below. Err - when the voltage or current is too low during the meter work: - Pf i , t i below 10% U n , I n below 10% U n - The full time intervał...
Page 27
Power consumption: - in the supply circuit 6 VA - in the voltage circuit 0.05 VA - in the current circuit 0.05 VA Display field 3 LED digits, 14mm height, red colour Relay output relay, voltageless, NOC contacts load capacity: 250 V~/ 0.5 A~ Serial interface RS-485 addres: 1..247;...
Page 28
- power factor -1 .. 0 .. 1 - ambient temperature - 25...23...+55 C - storage temperature - 30... +70 C - relative air humidity 25... 95% (condensation inadmissible) - admissible peak factor: - current - voltage - external magnetic field 0...
The version code is established by the manufacturer ORDER EXAMPLE The N14-2-2-00-7 code means: N14 – network parameter meter of N14 type 2 – input current 5 A (X/5) 2 – input voltage 3 x 230/400 V 00 – standard version...
11. MAINTENANCE AND GUARANTEE The N14 network parameter meter does not require any periodical maintenance. In case of some incorrect operations: 1. In the period of 12 months from the date of purchase: One should take the transducer down from the installation and return it to the Manufacturer’s Quality Control Dept.
Page 32
According to ISO 9001 and ISO 14001 international requirements. All our instruments have CE mark. For more information, please write to or phone our Export N14-09D Lubuskie Zak³ady Aparatów Elektrycznych LUMEL S.A. ul. Sulechowska 1, 65-022 Zielona Góra, Poland Materm d.o.o. tel: 02 608 90 10 info@materm.si...