Re-Calibrating The Touchscreen - GE IC755CxW07CD SERIES User Manual

Operator interface
Table of Contents

Advertisement

48
GFK-2847F
For public disclosure

5.1.3 Re-calibrating the Touchscreen

The QuickPanel
+
touchscreen is shipped pre-calibrated. However, If there are any issues
with touchscreen responsiveness, it may need to be re-calibrated.
� � To re-calibrate the touchscreen
Open the QuickPanel+ Setup tool.
1.
Select the TouchPanel tab.
2.
Select Recalibrate Touch Screen.
3.
Select Recalibrate Touch Sensor.
4.
Note During IC755CxW07CDx touchscreen sensor re-calibration, the user is
prompted to activate a switch located in the battery compartment. This is not
applicable to any other panel sizes.
5.
Remove the battery cover and press the switch.
Touchscreen Sensor Calibration Switch
Replace the battery cover.
6.
Switch
QuickPanel+ Operator Interface User Manual
Battery
Cover