Sample program 6
R7E3
R100
R1
DIF
R1
DFN
R7E3
To refresh receiving area with "Optional receiving mode"
(for EHV-CPU)
WM003 = H2
WM004 = H2F
DM005 = ADR (WM10)
WM007 = 13
R100 = 1
R100
SCRW (WM000, R100)
M252 = 1
R103 = 1
M252 = 0
R103 = 1
WM00B = H3
WM00C = H0
DM00D = ADR (WM20)
WM00F = 10
M242 = 1
R103 =1
SCRW (WM008, R103)
Chapter 7 Automatic Sending/Receiving function (ASR)
(00001)
Parameters setting of SCRW(s) for reading out SR.
Request to read out SR
Area setting (unit:0, slot:0)
Transmission I/O address is starting from WM10
Transmission data size is 13 words
Setting 1 to control bit for reading SR
(00002)
S
Reading out SR at R100 = 1
(00003)
SCRW for reading out SR
(00004)
Optional transmission is enabled for connection 3
(00005)
Optional transmission is disabled for connection 3
(00006)
Parameters setting of SCRW (s) for writing CR.
Request to write CR.
Area setting (unit:0, slot:0)
Transmission I/O address is starting from WM20.
Transmission data size is 10 words.
(00007)
SCRW for writing CR.