Hitachi EH-150 Applications Manual page 117

Ethernet module 2 eh-eth2
Hide thumbs Also See for EH-150:
Table of Contents

Advertisement

(2) Various kinds setting
Various kinds setting start
DIP SW bit 1 is ON
and Bit 2, 3 is OFF
DIP SW bit 4 to 8 are
There is response of
ping command
Online "EH-ETH2 Configurator"
Abnormal setting
Complete of various kinds setting
*1: Refer to "
CAUTION at the time of the module exchange
N
Y
Y
all OFF
N
N
Y
N
Y
Y
N
10-3
Chapter 10 Troubleshooting
Some parameters can be changed
only with the dip switch
configuration shown as left.
This DIP SW configuration is not
allowed to use.
The bit 4 to 8 is for the lowest
octet of IP address.
The network is not on line
physically or logically. Check the
below items.
- Communication cable and HUB
etc.
- Wrong IP address in the host
computer.
- Duplication of IP address to
other stations.
- MAC address is not solved.
Check if communication setting
of "EH-ETH2 Configurator" is
correct.
Set up an appropriate value
according to the error message.
" of "9.2 Regular Check".