Lennox BAC 030 SNM 3M Installation, Operating And Maintenance Manual page 93

Rooftop units air cooled baltic series
Hide thumbs Also See for BAC 030 SNM 3M:
Table of Contents

Advertisement

DISPLAY DM60
Heating mode set point visualization
Cooling mode set point visualization
Fresh air damper opening percentage visualization
Engaged compressor percentage visualization
Engaged heaters percentage visualization
• pressing the 'alarm' button directs you to the alarm list display.
• pressing the 'esc' button takes you to the main display.
• pressing the 'arrow' button directs you to the previous screen.
• pressing the 'down arrow' button directs you to the next screen.
Alarm list
History used to store the last 99 alarms occurred on the unit.
• each alarm is stored on the date and time the fault occurred.
• an active alarm is signifi ed by the 'bell' symbol.
• an reseted alarm is signifi ed by the '.' symbol.
• each alarm is signifi ed by a 3 digit code
To have the text of fault code, position the cursor on the desired line, by using the 'up arrow' or 'down arrow' and then confi rm by
pressing 'enter'
• pressing the 'esc' button takes you to the main display.
• pressing the 'arrow' button positions you in the list.
• pressing the 'enter' button takes you to the clear display of failure code.
• pressing the 'down arrow' button positions you in the list.
BALTIC-IOM-0412-E / Control manual
• 89 •