Lennox BAC 030 SNM 3M Installation, Operating And Maintenance Manual page 91

Rooftop units air cooled baltic series
Hide thumbs Also See for BAC 030 SNM 3M:
Table of Contents

Advertisement

DISPLAY DM60
Main
Top left :
Control in heating mode or
• Small, numerical value: volatile set point temperature: View and/or modify the offset, or set point, of the desired temperature control
for the selected rooftop. Pressing the 'arrow' button increases the set point value. Pressing the 'down arrow' button decreases the
set point value.
If the setpoint is changed, this value is maintained as long as the rooftop scheduling doesn't change modes (night, day, day I,
day II, BMS).
At each change of the mode the CLIMATIC™ 60 sets the value of this setpoint on the preset value in the mode concerned.
• Big, numerical value: measured air temperature value in the conditioned space.
Top right:
Ventilation state
Bottom right:
State mode based on the schedule, hour, minute, of CLIMATIC™ :
Night mode
Day mode
Day I mode
Day II mode
Bottom left:
If the unit is in alarm, this symbol is displayed
• Pressing the 'alarm' button directs you to the alarm list display.
• Pressing the 'prg' button directs you to rooftop setup menus display.
• Pressing the 'esc' button takes you to the selected rooftop choice display.
• Pressing the 'arrow' button increases the set point value.
• Pressing the 'enter' button takes you to the rooftop operation display.
• Pressing the 'down arrow' button decreases the set point value.
BALTIC-IOM-0412-E / Control manual
control in cooling mode
• 87 •