Lennox BAC 030 SNM 3M Installation, Operating And Maintenance Manual page 42

Rooftop units air cooled baltic series
Hide thumbs Also See for BAC 030 SNM 3M:
Table of Contents

Advertisement

eDrive™ VENTILATION
eDrive™ mounting
eDrive™ assembly is designed to have no adjustment to be made inside the machine
In case of vertical misalignment one could use metallic washer located under the motor to adjust height
Max angular misalignment 4°
eDrive™ coupling dimensions
Machine
Motor size
size
kW
C box
1,5
C box
2,2
C box
3
C box
4
C box
5,5
D box
2,2
D box
3
D box
4
D&E box
5,5 to 7,5
E box
9 to 11
eDrive™ airfl ow reading
eDrive is controling the airfl ow within the operating range of each kit.
Airfl ow rate calculation inputs are rpm and power absorbed output read on the inverter variable bus.
The airfl ow rate calculation formula is calibrated according lab tests.
• 38 •
Max radial misalignment 3mm
Motor shaft
Fan shaft
diameter
diameter
mm
mm
24
25
28
25
28
25
28
25
38
25
28
30
28
30
28
30
38
30
38
40
Max axial range 8 mm
Coupling
Coupling
Coupling type
reference
PP
2 x Taper lock bushing
PV40
2 x Taper lock bushing
PV40
PV40
2 x Taper lock bushing
2 x Taper lock bushing
PV40
2 x Taper lock bushing
PV60
1 Taper lock bushing + D30
PV50
1 Taper lock bushing + D30
PV50
1 Taper lock bushing + D30
PV50
1 Taper lock bushing + D38
PVP50
PV 60
2 x Taper lock bushing
Vibration absorbtion
Motor moteur
Fan taper
bushing
Ref
ref
28-20 al24
28-20 al25
28-20 al28
28-20 al25
28-20 al28
28-20 al25
28-20 al28
28-20 al25
40-25 a38
40-25 al25
30-25 al28
30-25 al30
30-25 al28
30-25 al30
30-25 al28
30-25 al30
30-25 al30
40-25 al 38
40-25 al 40
BALTIC-IOM-0412-E / Service manual