COMMISSIONING RECORD SHEET

Site details
Site
Unit Ref
Installer
(1) ROOF INSTALLATION
Suffi cient Access OK
Yes
No
(2) CONNECTIONS CHECK
Phase check
Yes
No
(3) CLIMATIC™ CONFIGURATION CHECK
CLIMATIC™ 60 Confi gured according to the options and specifi cations
Yes
No
(4) SUPPLY BLOWER SECTION
Type
Power displayed on plate
Voltage displayed on plate
Current displayed on plate
Fan type
Displayed coupling ref
Alignment checked
Fan speed
Averaged measured amps
Shaft mechanical mower
(Refer to airfl ow balancing)
Operating point checked
Read airfl ow
(5) AIRFLOW PRESSURE SENSOR CHECK
Measured pressure drop
(6) EXTERNAL SENSOR CHECKS
Check electrical connections
Supply temperature
Return temperature
Outdoor temperature
(7) MIXING AIR DAMPERS CHECKS
Dampers open & close freely
Yes
No
• 30 •
Condensate drain fi tted
Yes
Voltage between Phases
kW
V
A
Forward
mm
Yes
rpm
A
W
Yes
m
3
/h
Set points adjusted
Yes
If yes enter new values
mBar
3410:
Yes
No
% Minimum FA
%
Controller
Model
Serial No
Refrigerant
Roofcurb
No
OK
1/2
N°1
Backward
No
No
3411:
Check and record temp. in
menu 2110
100% Fresh Air
°C
°C
°C
Power
exhaust checked
Yes
No
Not OK
2/3
1/3
N°2
Forward
Backward
Yes
No
Yes
No
No
3412:
Yes
No
100% return Air
°C
°C
°C
Enthalpy sensor(s) checked
Yes
No