Balanced Flue Operation With The Vitocrossal 200 - Viessmann VITOCROSSAL 200 Type CM2 Technical Manual

Gas condensing boilers 87 to 1400 kw
Hide thumbs Also See for VITOCROSSAL 200 Type CM2:
Table of Contents

Advertisement

Design information

Balanced flue operation with the Vitocrossal 200

For balanced flue operation, the Vitocrossal 200 requires a flue pipe
between the gas condensing boiler and the shaft as well as for routing
through the shaft (type C
to TRGI 2008).
53
System size flue pipe 7 125, 150, 200 and 250 mm.
For routing through shafts or ducts with longitudinal ventilation
that meet the requirements for domestic chimneys to DIN V
18160-1, or have a fire rating of 90 min (L90).
8
3
9
E
3
1
A Secondary ventilation
B Flue gas
C Inspection port
D Minimum internal shaft dimension (see page 31)
E Ventilation air
Combustion air supply via vertical pipes
Rated heating
System size
output range in
Flue system
kW
Vitocrossal 200, type CM2
80 to 87
DN 125
80 to 87
DN 150
105 to 115
DN 150
105 to 115
DN 200
130 to 142
DN 150
130 to 142
DN 200
130 to 142
DN 200
170 to 186
DN 200
170 to 186
DN 200
Gas condensing boilers
(cont.)
B
E
A
2
2
3
3
4
3
2
2
3
4 7
6
3
A
5
B
2
2
3
3
C
5
2
D
3
5
3
Max. height in m
Ventilation
Balanced flue
air routing
DN 150
17
DN 150
30
DN 150
25
DN 150
30
DN 150
15
DN 150
27
DN 200
30
DN 150
11
DN 200
28
If the ventilation air supply is routed separately, use individual com-
ponents in the corresponding size for flue pipes.
A boiler flue connection must be ordered for the connection to the
Vitocrossal.
For system size diameter 125, 150, 200 and 250 mm
1
Boiler flue connection
(order separately)
Reducer
Extension
2
Basic shaft unit
comprising
– Support bend
– Support rail
– Shaft cover
– Spacers (5 pce)
Spacers (3 pce)
3
Pipe
– 2 m long (2 pce = 4 m long)
– 2 m long (1 pce)
– 1 m long (1 pce)
– 0.5 m long (1 pce)
4
Inspection piece
Straight (1 pce)
5
Flue bend
87° (1 pce)
45° (2 pce)
6
Ventilation bezel
(1 pce)
Flue bend
(for use in corbelled chimneys)
30° (2 pce)
15° (2 pce)
7
Inspection bend
87° (1 pce)
8
Ventilation bezel
(for ventilation air routing)
9
Ventilation air damper
(for ventilation air routing)
Rated heating
System size
output range in
Flue system
kW
225 to 246
DN 200
285 to 311
DN 250
Vitocrossal 300, type CT3U
370 to 400
DN 250
460 to 500
DN 250
575 to 630
DN 250
Max. height in m
Ventilation
Balanced flue
air routing
DN 200
11
DN 250
30
DN 250
30
DN 250
18
DN 250
5
VIESMANN
35
8