Installation accessories
7.1 Specification
Accessories for heating circuits
Divicon heating circuit distribution
For boilers up to 314 kW
Specification
Design and function
■ 1 to 4 heating circuits can be connected to the flow distributor and
return collector.
■ Free connections are closed via dummy flanges (part of the standard
delivery).
■ The flow distributor and return collector can optionally be arranged
on the r.h. or the l.h. side of the boiler.
■ Thermal insulation for the Divicon heating circuit distributor is part of
the standard delivery.
Divicon heating circuit distributor, installed adjacent to the boiler
for Vitocrossal 200 and 300
Do not use the prefabricated pipe connections for these boilers. The
Divicon heating circuit distributor can also be placed near the boiler
(as an alternative to wall mounting) by using the separate adjustable
feet and on-site pipe connections.
Divicon heating circuit distributor, wall mounted
for Vitocrossal 200 and 300
420
420
E
E
210
70
E
Drain
EL Air vent valve
Dimensions
Rated boiler heating output
a (DN 25 + DN 32)
b (DN 40 + DN 50)
c
Gas condensing boilers
420
EL
910
360
1630
kW
87 to
246 to
187
314
mm
1186
1196
mm
1586
1606
mm
170
173
EL
500
Connections for an additional consumer (e.g. DHW cylinder)
2 pipe connectors G 1½ (male thread) on the back of the flow distrib-
utor and return manifold.
= 307
c
VIESMANN
7
11