Stainless Steel Flue Gas Header For Two-Boiler System - Viessmann VITOCROSSAL 200 Type CM2 Technical Manual

Gas condensing boilers 87 to 1400 kw
Hide thumbs Also See for VITOCROSSAL 200 Type CM2:
Table of Contents

Advertisement

Design information

Stainless steel flue gas header for two-boiler system

For two-boiler systems up to 622 kW with the Vitocrossal 200, type CM2, 87 to 311 kW
Connection to the flue system, optional outlet on the l.h. or r.h. side.
500
D
c
F
Example: outlet on the r.h. side
A Boiler flue connection with test ports and inspection port
B Motorised flue gas damper
C Sliding element, 250 mm
D Tee connector
Dimensions
Nominal di-
mm
ameter
a
mm
b
mm
c
mm
d
mm
e
mm
f
mm
f max.
mm
Gas condensing boilers
(cont.)
c
D
500
E
C
B
A
f
200
250
200
250
150
200
350
400
279
328
333
368
820
860
1130
1220
1220
250
G
H
E Sliding element, 500 mm
F Inspection cover
G Flue pipe with condensate drain
H Flue system
Selection table for the max. draught 70 Pa
300
Rated heating output
(kW)
300
2x87, 2x115, 2x142
200
2x186, 2x246
400
2x311
328
368
Use a flue pipe with the same diameter as that of the flue gas
header.
860
C
B
A
e
Diameter of the effective vertical flue
pipe up to 30 metres (in mm)
7 200
7 250
7 300
VIESMANN
8
45

Hide quick links:

Advertisement

Table of Contents
loading