2.2 Positioning, installation
Installation conditions for balanced flue operation (boiler type C)
As device type C
, C
13x
33x
C
to TRGI '86/96, Vitodens can be
63x
installed for balanced flue operation,
independent of the size or ventilation of
the boiler room.
It may, for example, be installed in rooms
with personnel traffic or in living areas, in
ancillary rooms without ventilation, in
cupboards (open top) and niches without
maintaining minimum clearances to
combustible components as well as in
attic rooms (pitched attics and long pane
rooms of a roof) where the balanced flue
air supply/exhaust pipe can be directly
routed through the roof.
Since the flue pipe union for balanced
flue operation is surrounded by
2
combustion air (coaxial pipe), no
clearances towards combustible
components need to be maintained
(further details on page 100).
The installation location must be safe
from the risk of frost.
Provide a condensate drain and a
blow-off line for the safety valve in the
boiler room.
Electrical interlocks with extraction
devices (cooker hoods etc.) are not
required with balanced flue operation.
Vitodens 300 with 66 kW
Install Vitodens 300 with 66 kW in
accordance with the Combustion Order
(FeuVo) [or local regulations] in a
separate boiler room. Fit the mains
electrical isolator outside the installation
room.
Ventilation air and exhaust air apertures
are required in accordance with TRGI
(see page 99).
48
, C
, C
or
Installation in a garage
43x
53x
Tests by the Gaswärme Institutes e. V.,
Essen, have confirmed that Vitodens is
suitable for installations in garages
(certification on request).
When installing this boiler in garages,
maintain a distance between the floor and
the burner of at least 500 mm. Secure the
boiler on site with a bracket or deflector
against mechanical damage.
Operation of Vitodens in wet areas
Vitodens is approved for installation in
wet areas (e.g. bath or shower rooms)
(
protection IP X4 D, splash-proof
When installing Vitodens in wet areas,
observe the safety areas and minimum
wall clearances according to VDE 0100 or
local regulations (see also electrical
protection range on page 49). Vitodens
may be installed in protection area 1.