Mixer Extension Kit - Viessmann VITOCROSSAL 200 Type CM2 Technical Manual

Gas condensing boilers 87 to 1400 kw
Hide thumbs Also See for VITOCROSSAL 200 Type CM2:
Table of Contents

Advertisement

Control units
(cont.)
■ Condensing boilers with Viessmann balanced flue system:
Order the balanced flue pipe with connector for the flue gas temper-
ature sensor separately.
■ For condensing boilers with on-site flue pipe:
The aperture required for the flue pipe installation must be designed
and approved on site. Install the flue gas temperature sensor into a
stainless steel sensor well (on-site).
9

Mixer extension kit

Part no. 7441 998
Components:
■ Mixer motor with connecting cable (4.0 m long) for Viessmann mixer
DN 20 to 50 and R ½ to 1¼ (not for flanged mixers) and plug
■ Flow temperature sensor as contact temperature sensor with con-
necting cable (5.8 m long) and plug
■ Plug for heating circuit pump
Mixer motor
0
1 8
Specification
Rated voltage
Rated frequency
Power consumption
Safety category
IP rating
Mixer motor for flanged mixers
■ Part no. 9522 487
DN 40 and 50, without system plug and connecting cable
■ Part no. Z004344
DN 65 to 100, without system plug and connecting cable
Immersion temperature controller
Part no. 7151 728
May be used as a maximum temperature limiter for underfloor heating
systems.
The temperature limiter is installed into the heating flow and switches
the heating circuit pump OFF if the flow temperature is too high.
VIESMANN
76
Specification
Cable length
IP rating
Sensor type
Permissible ambient temperature
– During operation
– During storage and transport
Permissible ambient temperature
– During operation
– During storage and transport
Torque
Runtime for 90° ∢
Flow temperature sensor (contact sensor)
Secured with a tie.
Specification
IP rating
Sensor type
230 V~
Permissible ambient temperature
50 Hz
– During operation
4 W
– During storage and transport
II
IP 42 to EN 60529, ensure
through design/installation
For specification, see the "Mixer and mixer motors" datasheet.
3.5 m, fully wired
IP 60 to EN 60529; ensure
through design/installation
Viessmann NTC 20 kΩ, at
25 °C
0 to +250 °C
−20 to +70 °C
0 to +40 °C
−20 to +65 °C
3 Nm
120 s
4 2
6 6
IP 32D to EN 60529
Ensure through design/instal-
lation
Viessmann NTC 10 kΩ at
25 °C
0 to +120 °C
–20 to +70 °C
Gas condensing boilers

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents