deScripTion
RAYSTAT-CONTROL-10 is an electronic Pt 100 control thermostat with
display, advanced alarm facilities and the capability of switching large
currents (25 A)� The RAYSTAT-CONTROL-10 is designed to control
Pentair Thermal Management heating cable systems� Heating cable
can be controlled (switched ON/OFF) either directly by the RAYSTAT-
CONTROL-10 or via a contactor�
Direct switching of heating cables is possible for heating loads up to 25 A�
For heating loads greater than 25 A indirect switching via a suitably rated
contactor controlled by a RAYSTAT-CONTROL-10 is necessary� Installation
and all wiring must be in accordance with applicable regulations� The
device must be installed in non hazardous areas only� Pentair Thermal
Management offers other controls for use in hazardous areas�
Technical data
Supply voltage:
Main relay:
Heater operation on
sensor error:
Hysteresis:
Set point T range:
Accuracy:
Operating Temperature:
User interface:
Power terminals:
Alarm terminals:
Sensor terminals:
Heater terminals:
enclosure
Exposure Temperature:
Ingress Protection:
Entries:
Size:
Weight:
Material:
Lid fixing:
6
230 Vac� +10%/–10%, 50/60 Hz (6V
leakproof maintenance-free non-
rechargeable battery incl� for programming
without power supply)
max� 25 A, 250 Vac� Resistive
programmable: ON or OFF
programmable: 1K to 5K
0°C to + 150°C
±0,5 K at 5°C
–30°C (–20°C, VDE approved) to +40°C
ambient
4 x 7 segment digital display
4 push buttons
alarm relay, max� 2 A, 250 Vac�
(Potential free)
3 x 0,75 mm² to 4 mm²
(3 +
) x 0,75 mm² to 2,5 mm²
(3 +
) x 0,75 mm² to 2,5 mm²
(2 +
) x 0,75 mm² to 4 mm²
–40°C to +80°C
IP 65
2 x M25, 1 x M20, 1 x M16
120 x 160 x 90 (mm)
approx� 800 gr�
polycarbonate
4 captive screws