To alter any parameter shown in the display, press the + or – keys� This
will allow the parameter to be raised or lowered to the maximum or the
minimum in integer steps�
If you require to reset all parameters to their default value, press the +
and – keys together for about 2 sec� If this is succesful, the display will
show
3. parameters
The first parameter to show up during Set-up mode is the Set Point�
Other parameters, their default, minimum and maximum values are
shown in the below table:
parameter
Set Point (°C)
Hysteresis (K)
Low Temperature
Alarm Threshold
(°C)
High Temperature
Threshold (°C)
Heater Operation if
Sensor Error
Voltage Free
Operation
1
Max� Low Temp� Alarm is always smaller than Set Point minus
hysteresis�
2
Min� High Temp� Alarm is always larger than Set Point plus hysteresis�
3
Consider also max� exp� temp� of heating cable in table,to select an
appropriate High Temp� Alarm value� If one does not want the High
Temp� Alarm to be active, set the value to
150�
default
Value
3
1
1
0
65
1
0
displayed
code
0 (OFF)
, which comes after
min.
max.
0
150
1
–40
148
2
2
150
1 (ON)
0 (NO)
1 (YES)
5
1
3
13