4. installation of the sensor
20 mm
location
– as indicated in the system design documentation
– not on valves, flanges, supports, pumps or other heat sinks
– at the top of the pipe for thermally sensitive pipe contents (A)
– on lower quadrant of pipe 90° for single heating cable (B)
– on lower quadrant of pipe centrally between the heating cables if
they are two or more (C)
attachment of the sensor
– fix sensor firmly on surface with adequate fixing tape (same tape as
used to fix heater to the pipe) in two places (D)
– fix sensor parallel to pipe (D)
– route sensor cable and eventual extension cable to avoid damage in
use� Fix to pipe with adequate tape where appropriate�
Warning: Do not install sensor at ambient temperatures below –20°C� Do
not bend sensor (last 50 mm), keep it straight under all circumstances�
Min� bending radius for sensor cable: 10 mm�
Wiring sensor to raySTaT-conTrol-10
Enter the sensor cable through the indicated M16 gland 5 and wire as
shown in the wiring diagram (page 37)� Please pay attention to color
coding of the wiring�