PARTS INSTALLATION
Number
Name of Accessories
1
Installation plate
2
Clip anchor
3
Self-tapping screw A ST3.9X25
4
Seal
5
Drain joint
Liquid side
Connecting
pipe
Gas side
Assembly
7
Remote controller
8
Self-tapping screw B ST3.9X10
9
Remote controller holder
NOTES
Except the above parts provided, the other parts needed
during installation you must purchase.
CAUTIONS
• Ensure that the space around the left and right of the
indoor unit is more than 12cm.
The indoor unit should be installed allowing a minimum
clearance of 15cm from the ceiling.
• Use a stud finder to locate studs to prevent unnecessary
damage to the wall.
• A minimum pipe run of 3 metres is required to minimise
vibration & excessive noise.
The indoor unit should be installed on the wall at a
height of 1.7 metres or more from the floor but less
than 2.3 metres from the floor.
• Directions A, B and C should be free from obstructions.
NOTES
• This illustration is for explanation purposes only.
• Copper lines must be insulated independently.

INSTALLATION PROCEDURE

INDOOR UNIT
I Fixing
• Place the installation guide pattern on the designated
installation place and mark the hole position.
• Drill a hole and mount installation plate.
• After determining the pipe
hole position. Drill the hole
at a slight downward slant
towards the outdoor side.
Note: When installing
the refrigerant pipes from
others side. A hole must
be place to allow fall
towards the outdoor unit.
J190
Q'ty
1
8
8
1
1
ø6.35
Parts you
ø 9.53 (9000Btu/h model)
must
purchase
ø12.7(12000Btu/h model)
1
2
1
ø 65 mm
Outdoor
Indoor
9
3
2
A
B
7
On/Off
Auto
Mode
SET TEMP
Fan
Sleep
Swing
ON TIMER
Air Direction
Hr.
Off TIMER
Timer On
Hr.
Timer Off
• Make 6 mm 4-6 holes, in the wall at the four corners of mounting
plate (bracket) then insert appropriate mounting devices.
• Install the mounting plate using 4-6 pieces of mounting screw
securely at four corners and tighten the screw completely.
Do not over tighten the screws and deform the back plate.
MODEL 07-09
Above 15cm from the ceiling
Outline of the Indoor Unit
Above 12cm
from the wall
Rear-left Pipe
70
Hole 65
750
MODEL 12
Above 15cm from the ceiling
Outline of the Indoor Unit
Above 12cm
from the wall
270~370
Rear-left Pipe
659
Hole 65
878
2/03/2005, 4:55 AM
1
6
Loop the
connective
cable.
C
Mounting screw B
ST3.9x10-C-H
9
8
Remote controller
holder
Installation Plate
Above 12cm
from the wall
Rear-right Pipe
70
Hole 65
Installation Plate
Above 12cm
40
from the wall
Rear-right Pipe
133
Hole 65