Allen-Bradley MicroLogix 1400 User Manual page 80

Hide thumbs Also See for MicroLogix 1400:
Table of Contents

Advertisement

Chapter 4
Communication Connections
66
MicroLogix 1400 Channel 0 to Modem Cable Pinout
When connecting MicroLogix 1400 Channel 0 to a modem using an RS-232
cable, the maximum that the cable length may be extended is 15.24 m (50 ft).
DTE Device
(MicroLogix
1400
Channel 0)
8-Pin
7
TXD
4
RXD
2
GND
1
B(+)
8
A(-)
5
DCD
6
CTS
3
RTS
ATTENTION: Do not connect pins 1 and 8. This connection will
cause damage to the RS-232/485 communication port (channel 0)
of the MicroLogix 1400 and/or the controller itself.
Constructing Your Own Modem Cable
If you construct your own modem cable, the maximum cable length is 15.24 m
(50 ft) with a 25-pin or 9-pin connector. Refer to the following typical pinout for
constructing a straight-through cable:
AIC+ Optical Isolator
or 1766-LEC Channel 2
9-Pin
3
TXD
2
RXD
5
GND
1
CD
pins 4 and 6
4
DTR
are internally
6
DSR
connected for
1766-LEC only
8
CTS
7
RTS
TXD
RXD
GND
DCD
DTR
DSR
CTS
RTS
Rockwell Automation Publication 1766-UM001I-EN-P - June 2015
DCE Device
(Modem,
PanelView,
etc.)
25-Pin
9-Pin
2
3
3
2
7
5
8
1
20
4
6
6
5
8
4
7
Modem
25-Pin
9-Pin
TXD
2
3
RXD
3
2
GND
7
5
CD
8
1
DTR
20
4
DSR
6
6
CTS
5
8
RTS
4
7

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents