(1) Sinking/Sourcing Inputs - Sourcing/sinking describes the current flow between the I/O module and the field device. Sourcing I/O circuits supply (source) current to sinking
field devices. Sinking I/O circuits are driven by a current sourcing field device. Field devices connected to the negative side (DC Common) of the field power supply are
sinking field devices. Field devices connected to the positive side (+V) of the field supply are sourcing field devices.
(2) Refer to Publication 1762-IN10, MicroLogix 1762-IQ16 DC Input Module Installation Instructions, for the derating chart.
(3) Only applicable to Series B I/O modules.
Output Specifications
Specification
1762-OA8
Shipping weight, approx.
215 g (0.48 lbs.)
(with carton)
Voltage category
100...240V AC
Operating voltage range
85...265V AC at
47...63 Hz
Number of outputs
8
Bus current draw, max.
115 mA at 5V DC
(0.575 W)
Heat dissipation, max.
2.9 W
Signal delay, max. –
On delay: 1/2 cycle
resistive load
Off delay: 1/2 cycle
Off-state leakage current,
2 mA at 132V,
max.
2.5 mA at 265V
On-state current, min.
10 mA
On-state voltage drop,
1.5V at 0.5 A
max.
Continuous current per
0.25 A at 55 °C
point, max.
(131 °F)
0.5 A at 30 °C (86 °F)
Continuous current per
1.0 A at 55 °C (131 °F)
common, max.
2.0 A at 30 °C (86 °F)
Continuous current per
2.0 A at 55 °C (131 °F)
module, max.
4.0 A at 30 °C (86 °F)
Surge current, max.
5.0 A (Repeatability is
once every 2 s for a
duration of 25 ms.
Isolated groups
Group 1: Outputs 0 to
3
Group 2: Outputs 4 to
7
Rockwell Automation Publication 1766-UM001I-EN-P - June 2015