Troubleshooting

8
Troubleshooting
8.1

Error messages and warning messages

If an error occurs in the device, the color of the status LED changes from green to red and the
illumination of the digital display changes from white to red. A status LED flashing red and
green signals a warning. The display shows:
• E-code for errors
In the event of an error message, the measured value is uncertain.
• W-code for warnings
In the event of a warning, the measured value is reliable.
Code
Explanation
E011
Device configuration faulty
E012
Error in measurement or medium temperature outside
measurable range
E013
Sensor heating defective
E019
Power supply outside specification
E015
E020
Memory error
E021
E022
Power is only supplied to the device via the
communication interface (measurement is deactivated)
E042
Output current can no longer be generated (only for 4
to 20 mA output, e.g. load at analog output too high or
open analog output)
32
Remedy
Reset device (→ Chap. 5.1.10)
Check medium temperature, return device
to Endress+Hauser where necessary
Return device to Endress+Hauser
Check operating voltage
Return device to Endress+Hauser
Check operating voltage
Check load; switch off analog output
DTT31, DTT35