Johnson Controls TRUE RH HC-67x3 Installation Instructions Manual

True rh series humidity controller

Advertisement

Quick Links

Application Requirements
The HC-67x3 Humidity Controllers proportionally
ramp their output as the humidity changes in the
proportional band. The setpoint is at the low end of
the proportional band for Direct Acting (DA) and at
the high end for Reverse Acting (RA) (shown in
Figure 1) for both wall mount and duct probe
humidity controllers.
V Out
Proportional
Band
10
5
0
0
Setpoint
Figure 1: 0 to 10 Volt, RA Application
Configure the controller prior to installation for the
following: setpoint, proportional band, action, and
output signal. Proceed to the appropriate controller
section.
© 2014 Johnson Controls, Inc.
Part No. 24-7701-179, Rev. A
T
RUE
HC-67x3 Humidity Controllers
Note: The actual output
voltage may exceed 10 VDC.
100% RH
Installation Instructions HC-67x3
RH™ Series
Installation
IMPORTANT:
Controllers is intended to provide an input to
equipment under normal operating conditions. Where
failure or malfunction of the HC-67x3 Series Humidity
Controllers could lead to personal injury or property
damage to the controlled equipment or other property,
additional precautions must be designed into the
control system. Incorporate and maintain other
devices, such as supervisory or alarm systems or
safety or limit controls, intended to warn of or protect
against failure or malfunction of the HC-67x3 Series
Humidity Controllers.
IMPORTANT:
Controllers est destiné à transmettre des données
entrantes à un équipement dans des conditions
normales de fonctionnement. Lorsqu'une défaillance
ou un dysfonctionnement du HC-67x3 Series Humidity
Controllers risque de provoquer des blessures ou
d'endommager l'équipement contrôlé ou un autre
équipement, la conception du système de contrôle doit
intégrer des dispositifs de protection supplémentaires.
Veiller dans ce cas à intégrer de façon permanente
d'autres dispositifs, tels que des systèmes de
supervision ou d'alarme, ou des dispositifs de sécurité
ou de limitation, ayant une fonction d'avertissement ou
de protection en cas de défaillance ou de
dysfonctionnement du HC-67x3 Series Humidity
Controllers.
The controller is available in both a wall mount or duct
probe package to suit a variety of sensing application
needs. Refer to the Mounting section for a complete list
of the tools required for installation.
Parts Included
mounting base for U.S. wallbox or surface mounting
No. 6-32 x 7/8 in. oval-head screw (2)
No. 4-40 x 1/4 in. hex-head cover screw (in the
mounting base)
drywall clip mounting kit (includes two each
No. 6-20 x 1.25 in. pan-head tapping screws, spring
clips, and spacers)
Issue Date June 2, 2014
The HC-67x3 Series Humidity
Le HC-67x3 Series Humidity
www.johnsoncontrols.com
1

Advertisement

loading

Summary of Contents for Johnson Controls TRUE RH HC-67x3

  • Page 1 No. 4-40 x 1/4 in. hex-head cover screw (in the mounting base) • drywall clip mounting kit (includes two each No. 6-20 x 1.25 in. pan-head tapping screws, spring clips, and spacers) © 2014 Johnson Controls, Inc. Part No. 24-7701-179, Rev. A www.johnsoncontrols.com...
  • Page 2 Allen-head Adjustment Tool (30/bag) TE-67MB-600 Mounting Base Kit TE-67D0-601** Door Replacement Kit with Johnson Controls logo TE-67D0-602** Door Replacement Kit without logo * These foam pads help prevent drafts from entering the unit through the wall and make installation easier when mounting on an uneven surface.
  • Page 3 needed as shown in Figure 6. Do not use the Cover spacers for 5/8 in. (16 mm) drywall. Screw Note: For replacement spring clips, spacers, and screws, order the ACC-DWCLIP-0 Drywall Clip Mounting Kit. (See Table 1.) Cover Screw Cover Base Figure 4: Attaching the Cover to the Base Note: Once installed, the unit cannot be removed...
  • Page 4 Drywall 1-3/8 in. Spacer (2) for Base (35 mm) 3/8 in. (9.5 mm) and 1/2 in. Hole (12.7 mm) Thick Drywall 1-3/8 in. (35 mm) Hole Drywall Drywall Spring Clip (2) Spring Clip (2) No. 6-20 x 1.25 in. Pan-head Tapping Screw (2) Figure 6: Surface Mounting to Drywall 2.
  • Page 5: Setup And Adjustments

    Wiring Action Output 0 to 10 VDC Reverse CAUTION: Risk of Electric Shock. (Factory Set) (Factory Set) Disconnect the power supply before making electrical connections to avoid electric shock. 6 to 9 VDC Direct MISE EN GARDE: Risque de décharge électrique. Débrancher l'alimentation avant de réaliser tout Power raccordement électrique afin d'éviter tout risque de...
  • Page 6: Troubleshooting

    To order the setpoint or proportional band potentiometer to replacement parts, contact the nearest the desired setting. Johnson Controls representative. 2. Select the appropriate control action and output setting using the jumpers. RH Series HC-67x3 Humidity Controllers Installation Instructions...
  • Page 7: Technical Specifications

    The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products.