Alert messages

iPDU alarms

The iPDU enables you to send an email notification or SNMP trap to specified recipients if a certain alert
situation prevails.
The following table lists information for all alarm messages.
Alarm text
Display Communication
Error
Load Segment Current
Managed Ext. Bar
Communication Error
Topology Discovery Error
PDU Voltage High*
PDU Voltage Low*
Phase Load
Total PDU Load
Redundancy
* Input voltage alarms for NA/JPN model iPDUs are based on voltage specifications regulated in the United States
(from 188 volts to 228 volts). In Japan, the regulated voltage is from 182 volts to 222 volts.
Description
The Display Unit can no longer
communicate with the iPDU.
The current for the circuit breaker
is above the warning or critical
limit.
An Intelligent Extension Bar can no
longer communicate with the iPDU.
An outlet device on an Intelligent
Extension Bar can no longer
communicate with the iPDU.
The voltage for the iPDU is above
the warning or critical limit.
The voltage for the iPDU is below
the warning or critical limit.
The phase load is above the
warning or critical limit.
The total load of the iPDU is above
the warning or critical limit.
The iPDU cannot communicate with
the redundant PDU or there is a
redundancy configuration error.
Recommendation
Check the communication link.
Relocate a load to a different load
segment.
Check the communication link.
Check the communication link.
Check the iPDU input voltage.
Check the iPDU input voltage.
Balance the loads across all available
load segments.
Consider moving a load to a different
iPDU.
Check the status of the redundant PDU
and the configuration settings for each
iPDU.
Alert messages 74