Connecting devices

When connecting devices, distribute the loads evenly across the phase to remain within the capability of
the Extension Bars and Core Unit. Do not overload the iPDU. The total current rating of all equipment
connected to each output cannot exceed the total output rating marked on the iPDU.
Core Unit
AF520A
NA/JPN
AF521A
NA/JPN
AF522A
NA/JPN
AF533A
NA/JPN
AF523A
NA/JPN
AF525A
INTL
AF526A
INTL
AF527A
INTL
* For 3 phase iPDUs, each phase is defined as follows:
– Phase A—Load segment 1 and load segment 4
– Phase B—Load segment 2 and load segment 5
– Phase C—Load segment 3 and load segment 6
Input rating of
Max branch
Core Unit
circuit
breaker
rating
24 A
30 A
Single phase
40 A
50 A
Single phase
24 A
30 A per
phase
3 phase
40 A
50 A per
phase
3 phase
48 A
60 A per
phase
3 phase
32 A
32 A
Single phase
16 A
16 A per
phase
3 phase
32 A
32 A per
phase
3 phase
Individual
Load circuit
outlet rating
breaker
and style
rating
16 A IEC-320
20 A
C19
16 A IEC-320
20 A
C19
16 A IEC-320
20 A
C19
16 A IEC-320
20 A
C19
16 A IEC-320
20 A
C19
16 A IEC-320
16 A
C19
16 A IEC-320
16 A
C19
16 A IEC-320
16 A
C19
Installing the HP Intelligent Power Distribution Unit 29
Individual
phase rating*
24 A
40 A
13.86 A per
phase
23.1 A per
phase
27.71 A per
phase
32 A
16 A per
phase
32 A per
phase