Indoor Unit Room Sensor Error (Open/Short) - Samsung AM007FN1DCH/AA Service Manual

System airconditioner
Hide thumbs Also See for AM007FN1DCH/AA:
Table of Contents

Advertisement

Troubleshooting

4-4-3 Indoor Unit ROOM sensor Error (Open/Short)

Outdoor unit display
Indoor unit display
Criteria
Cause of problem
1. How to check
Is indoor room temperature sensor
connector dislocated?
After separating indoor room
temperature sensor connector from PCB,
measure the resistance values between
both terminals
is the resistance value significantly
deviated from the temp. table?
Re-start after replacing PCB.
4-38
x x x ( x x x : The address of the error occurred indoor unit )
◑ (Timer)
×(Operation)
• Refer to how to determine below
• The room temperature sensor of No. XXX indoor unit has defective OPEN/SHORT
Yes
Ex) Room temp. 26°C – Resistance 0.926KΩ
Yes
At that time,
Yes
×(Fan)
×(Filter)
×(Defrost)
No
Re-start after connecting
the connector to the PCB.
No
As it is due to an indoor oom temperature
sensor defect, replace it.
Temperature
Resistance
(°C)
(KΩ)
70
2.2
60
3.0
50
4.2
40
5.8
30
8.3
21
12.1
10
18.0
0
27.3
-10
43.0
Samsung Electronics

Hide quick links:

Advertisement

Table of Contents

Troubleshooting

loading

This manual is also suitable for:

Am012fn1dch/aaAm009fn1dch/aaAm018fnndch/aaAm009fnndch/aaAm020fnndch/aaAm012fn4dch/aa ... Show all

Table of Contents