Summary of Contents for Samsung AM007FNTDCH

  • Page 2: Table Of Contents

    A Contents INSTALLATION PARTS Safety precautions ..............................3 Accessories ..................................5 Selecting the installation location ..........................6 Indoor unit installation .............................7 Purging the unit ................................8 Connecting the refrigerant pipe ..........................9 Cutting/flaring the pipes ............................10 Performing leak test & insulation ........................11 Drain hose installation ............................12 Charging direction of the drain hose .........................
  • Page 3: Safety Precautions

    This manual explains how to install an indoor unit with a split system with two SAMSUNG units. The use of other types of units with different control systems may damage the units and invalidate the warranty. The manufacturer shall not be responsible for damages arising from the use of non compliant units.
  • Page 4 Safety precautions Our units must be installed in compliance with the spaces indicated in the installation manual to ensure either accessibility from both sides or ability to perform routine maintenance and repairs. The units’ components must be accessible and that can be disassembled in conditions of complete safety either for people or things. For this reason, where it is not observed as indicated into the Installation Manual, the cost necessary to reach and repair the unit (in safety, as required by current regulations in force) with slings, trucks, scaffolding or any other means of elevation won’t be considered in-warranty and charged to end user.
  • Page 5: Accessories

    A Accessories The following accessories are supplied with the indoor unit. The type and quantity may differ depending on the specifications. Installation Plate Remote Control Batteries for Installation manual Remote Control User's manual...
  • Page 6: Selecting The Installation Location

    A Selecting the installation location Indoor Unit Where airflow is not blocked. Where cool air can be distributed throughout the room. Install the refrigerant piping length and the height difference of both indoor and outdoor units as indicated in the installation diagram. Wall that prevents vibration and is strong enough to hold the product weight.
  • Page 7: Indoor Unit Installation

    Indoor unit installation Before fixing the installation plate to the wall or window frame, you must determine the position of the 65mm hole through which the cable, pipe and hose pass to connect the indoor unit to the outdoor unit. When facing the wall, the pipe and cable can be connected from the: Right...
  • Page 8: Purging The Unit

    A Purging the unit Upon delivery, there may be inert gas inside the indoor unit. Purge the gas from the indoor unit before connecting the assembly pipe. Unscrew the caps at the end of each pipe. Result: All inert gas exhausts from the indoor unit. To prevent dirt or foreign substances from getting into the pipes during installation, do NOT remove the caps completely until you are ready to connect the pipes.
  • Page 9: Connecting The Refrigerant Pipe

    Connecting the refrigerant pipe Connect indoor and outdoor units with field-supplied copper pipes by means of flare connections. Use insulated seamless refrigeration grade pipe only, (Cu DHP type according to ISO1337), degreased and deoxidized, suitable for operating pressures of at least 4200 kPa and for burst pressure of at least 20700 kPa.
  • Page 10: Cutting/Flaring The Pipes

    Cutting/flaring the pipes Make sure that you prepared the required tools. (pipe cutter, reamer, flaring tool and pipe holder) If you want to shorten the pipe, cut it using a pipe cutter ensuring that the cut edge remains at 90° with the side of the pipe. There are some examples of correctly and incorrectly cut edges below.
  • Page 11: Performing Leak Test & Insulation

    A Performing leak test & insulation Leak test LEAK TEST WITH NITROGEN (before opening valves) In order to detect basic refrigerant leaks, before recreating the vacuum and recirculating the R410A, it’s responsible of installer to pressurize the whole system with nitrogen (using a pressure regulator) at a pressure above 4.1MPa (gauge).
  • Page 12: Drain Hose Installation

    A Drain hose installation When installing the drain hose for the indoor unit, check if condensation draining is adequate. When passing the drain hose through the 65-mm hole drilled in the wall, check the following: less Ditch Do NOT place the end The hose must The end of the drain Do NOT bend the hose...
  • Page 13: Changing Direction Of The Drain Hose

    Changing direction of the drain hose You can select the direction of the drain hose, depending on where you want to install the indoor unit. Detach the rubber cap with the flyer. Screw hole Screw Detach the drain hose by pulling it and turning to the left. Drain hose Insert the drain hose by fixing it into the groove of the drain hose and the outlet of the drain pan.
  • Page 14: Wiring Work

    Wiring work Power and communication cable connection Before wiring work, you must turn off all power source. Indoor unit power should be supplied through the breaker( ELCB or MCCB+ELB ) separated by the outdoor power. ELCB:Earth Leakage Circuit Breaker MCCB:Molded Case Circuit Breaker ELB:Earth Leakage Breaker The power cable should be used only copper wires.
  • Page 15 Specification of electronic wire Power supply MCCB ELB or ELCB Power cable Earth cable Communication cable X A, 30mmA Max : 242V 2.5mm 2.5mm 0.75~1.5mm Min : 198V 0.1 s Decide the capacity of ELCB(or MCCB+ELB) by below formula. Power supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene sheathed flexible cord.
  • Page 16 A Wiring work(Cont.) CAUTION Select the power cable in accordance with relevant local and national regulations. Wire size must comply with local and national code. For the power cable, use the grade of H07RN-F or H05RN-F materials. You should connect the power cable into the power cable terminal and fasten it with a clamp. The unbalanced power must be maintained within 10% of supply rating among whole indoor units.
  • Page 17: Setting An Indoor Unit Address And Installation Option

    A Setting an indoor unit address and installation option Set the indoor unit address and installation option with remote controller option. Set the each option separately since you cannot set the ADDRESS setting and indoor unit installation setting option at the same time. You need to set twice when setting indoor unit address and installation option.
  • Page 18 A Setting an indoor unit address and installation option (Cont.) Option setting Status 1. Setting SEG2, SEG3 option Press Low Fan button( ) to enter SEG2 value. Press High Fan button( ) to enter SEG3 value. SEG2 SEG3 Each time you press the button, …...
  • Page 19 Option setting Status 1. Setting SEG16, SEG17 option Press Low Fan button( ) to enter SEG16 value. Press High Fan button( ) to enter SEG17 value. SEG16 SEG17 Each time you press the button, … will be selected in rotation. 2.
  • Page 20 A Setting an indoor unit address and installation option (Cont.) Setting an indoor unit address (MAIN/RMC) Indoor Unit 1(L) Check whether power is supplied or not. 2(N) - When the indoor unit is not plugged in, there should be additional power supply in the indoor unit.
  • Page 21 Setting an indoor unit installation option (suitable for the condition of each installation location) Check whether power is supplied or not. Indoor Unit - When the indoor unit is not plugged in, there should be additional 1(L) power supply in the indoor unit. 2(N) The panel(display) should be connected to an indoor unit to receive option.
  • Page 22 A Setting an indoor unit address and installation option (Cont.) The output of hot water heater in SEG9 is generated from the hot coil part of the terminal board in duct models. * The output of hot coil terminal is AC 220 V / 230 V (The same as Indoor Unit’s input Power) 1(L) 2(N) COM1...
  • Page 23 Option SEG13 SEG14 SEG15 SEG16 SEG17 SEG18 Setting the output of external control / Explanation PAGE Use of external control S-Plasma ion Buzzer control Hours of filter usage External heater On/Off signal Remote Controller Display Details Setting the External Indication Details Indication Details Indication Indication Details Indication...
  • Page 24 A Setting an indoor unit address and installation option (Cont.) Advanced function: Controlling cooling/heating current or power saving with motion detect. (*1) Minimizing fan operation when thermostat is off - Fan operates for 20 seconds at an interval of 5 minutes in heat mode. (*2) 1: Fan is turned on continually when the hot water heater is turned on, 3: Fan is turned off when the hot water heater is turned on with cooling only indoor unit Cooling only indoor unit: To use this option,install the Mode Select switch(MCM-C200) on the outdoor unit and fix it as cool mode.
  • Page 25 05 series installation option(Detailed) Option No. : 05XXXX-1XXXXX-2XXXXX-3XXXXX Option SEG1 SEG2 SEG3 SEG4 SEG5 SEG6 (When setting SEG3) Use of Auto Change (When setting SEG3) (When setting SEG3) Standard for mode PAGE MODE Explanation Over for HR only in Standard heating Standard cooling change Auto mode...
  • Page 26 Setting an indoor unit address and installation option (Cont.) (*3) Option SEG13 SEG14 SEG15 SEG16 SEG17 SEG18 Explanation Control variables when using hot water / external heater Remote Controller Display Details Indication Set temp. for heater On/Off Delay time for heater On At the same time as thermo on No delay 10 minutes...
  • Page 27: Changing A Particular Option

    SEG 3, 4, 5, 6, 8, 9 additional information When the SEG 3 is set as "1" and follow Auto Change Over for HR only operation, it will operate as follows. Standard temp. for Temp. → Heating Cooling Standard temp. for Cooling Set temp.
  • Page 28: Final Check And Trial Operation

    Final check and trial operation To complete the installation, perform the following checks and tests to ensure that the air conditioner operates correctly. Check the following: Strength of the installation site Tightness of pipe connection to detect gas leak Electric wiring connection Heat-resistant insulation of the pipe Drainage Grounding conductor connection...
  • Page 29 Troubleshooting(Cont.) Flickering If you turn off the air conditioner when the LED is flickering, the LED is also turned off. If you re-operate the air conditioner, it operates normally at first, then detect an error again. When E108 error occurs, change the address and reset the system.Ex.) When address of the indoor unit #1 and #2 are set as 5, address of the indoor unit #1 will become 5 and indoor unit #2 will display E108, A002.
  • Page 30: Connecting Power And Communication Cable

    Connecting power and communication cable How to connect your extended power cables 1. Prepare a compressor and the following tools. Tools Crimping pliers Connection sleeve (mm) Insulation tape Contraction tube (mm) Spec MH-14 20xØ6.5(HxOD) Width 19mm 70xØ8.0(LxOD) Shape 2. As shown in the figure, peel off the shields from the rubber or wire of the power cable.
  • Page 31 5. Wrap it with the insulation tape twice or more and position your contraction tube in the middle of the insulation tape. A total of three or more layers of insulation is required. Method 1 Method 2 Insulation tape Insulation tape 40 mm 35 mm 6.