3. Lifting Method.

When the unit is to be lifted and moved, attach ropes to the hoisting
hangers (4 pieces) provided on the top corners of the unit.
When the unit is lifted, its center of gravity tends to shift the unit to
one side. Imbalance such as that in the figure should be attained.
The angles at which the ropes suspend the unit should be at
least 60º at the compressor end and at least 45º at the condenser
end. Care should be taken to avoid contact with the unit while it is
being lifted.

4. Drain Piping.

(1) The condensate drain fitting (R1) is provided. The drain pipe can
be led out at the right or left side. Please see Chapter 10:
Outlines & Dimensions for further details.
(2) The drain pipe must be provided with a trap on the outside of
the unit and also installed at an incline for proper drainage, as
shown below.
(3) To prevent condensate formation and leakage, provide the drain
pipe with insulation to safeguard against sweating.
(4) Upon completion of the piping work, check that there is no
leakage and that the water drains off properly.

5. Refrigerant Charge

An additional charge is unnecessary.
The table below shows the amount of the charge when the unit is shipped from the factory.
Refrigerant charge
per circuit (kg)
Refrigerant charge
per circuit (kg)
Refrigerant charge
per circuit (kg)
Refrigerant charge
per circuit (kg)
Refrigerant charge
per circuit (kg)
Refrigerant charge
per circuit (kg)
Refrigerant charge
per circuit (kg)
Refrigerant charge
per circuit (kg)
ART55A
ART60A
3.6
5.2
ART200A
ART250A
2 x 5.9
2 x 10.5
ART55AR
ART60AR
3.9
4.5
ART200AR
ART250AR
2 x 5.6
2 x 10.0
A4RT60A
A4RT80A
4.6
4.6
A4RT200A
A4RT250A
2 x 4.2
2 x 9.6
A4RT60AR
A4RT80AR
4.3
5.2
A4RT200AR
A4RT250AR
2 x 5.8
2 x 9.4
The drain piping should have a drain trap.
ART80A
ART100A
4.0
5.9
ART300A
ART360A
2 x 10.4
16.5 , 19.5
ART80AR
ART100AR
4.7
5.6
ART300AR
ART360AR
2 x 9.4
13.5 , 16
A4RT100A
A4RT120A
5.9
5.6
A4RT300A
A4RT360A
2 x 10.4
14.5 , 18.0
A4RT100AR
A4RT120AR
6.0
6.0
A4RT300AR
A4RT360AR
2 x 9.6
13.5 , 16
29
Hook (as directly aligned
over the center of gravity
as possible)
ART120A
ART150A
6.2
2 x 4.5
ART420A
2 x 19.5
ART120AR
ART150AR
6.0
2 x 4.7
ART420AR
2 x 16.4
A4RT150A
2 x 3.9
A4RT420A
2 x 18.0
A4RT150AR
2 x 5.0
A4RT420AR
2 x 16